Mitsubishi Electronics FR-S500 Single-phase 100V power supply, Specification list

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 182
Image 182
(3) Single-phase 100V power supply

Specification list

(3) Single-phase 100V power supply

Type FR-S510WE- K-NA

 

0.1

 

0.2

 

0.4

 

0.75

 

 

 

 

 

 

 

 

 

 

 

Applied motor capacity (*1)

 

kW

0.1

 

0.2

 

0.4

 

0.75

 

 

 

 

 

 

 

 

 

 

HP

1/8

 

1/4

 

1/2

 

1

 

 

 

 

 

 

Output

Rated capacity (kVA) (*2)

 

0.3

 

0.5

 

1.0

 

1.6

 

 

 

 

 

 

 

 

 

 

Rated current (A)

 

0.8

 

1.4

 

2.5

 

4.1

 

 

 

 

 

 

Overload current rating (*3)

 

150% 60s, 200% 0.5s (Inverse time characteristics)

 

Voltage

 

 

Three phase, 200V to 230V (*4, 6)

 

supply

Rated input AC voltage/frequency

Single-phase, 100V to 115V 50Hz/60Hz

 

 

 

 

 

 

 

 

 

 

Permissible AC voltage fluctuation

 

 

90 to 132V 50Hz/60Hz

 

 

 

 

 

Power

Permissible frequency fluctuation

 

 

 

±5%

 

 

 

 

 

 

 

 

 

 

 

 

Power supply system capacity

 

0.5

 

0.9

 

1.5

 

2.5

 

 

 

 

 

 

(kVA) (*5)

 

 

 

 

 

 

 

 

 

 

 

 

 

Protective structure (JEM1030)

 

 

 

Enclosed type (IP20)

 

 

 

 

 

 

 

Cooling system

 

 

 

Self-cooling

 

Approximate mass (kg (lbs))

 

0.6

 

0.7

 

0.9

 

1.6

 

(1.32)

 

(1.54)

 

(1.98)

 

(3.52)

 

 

 

 

 

 

 

*1. The applied motor capacity indicated is the maximum capacity applicable when a Mitsubishi 4-pole standard motor is used.

*2. The rated output capacity indicated assumes that the output voltage is 230V.

*3. The % value of the overload current rating indicates the ratio of the overload current to the inverter's rated output current.

For repeated duty, allow time for the inverter to return to or below the temperatures under 100% load.

*4. For single-phase 100V power input, the output voltage provided cannot be twice or more than the power supply voltage.

*5. The power supply capacity changes with the values of the power supply side inverter impedances (including those of the input reactor and cables).

*6. For single-phase 100V power input, the application of motor load reduces the output voltage about 10 to 15%. Therefore, the load must be reduced when a general-purpose motor is used.

172