1.2.2Cables, wiring length, and crimping terminals

Main circuit terminals

1.2.2Cables, wiring length, and crimping terminals

The following table indicates a selection example for the wiring length of 20m (65.62 feet).

1) Three-phase 200V power input

 

 

 

Ter-

 

Tight-

 

 

 

Crimping

 

 

 

Cable

 

PVC Insulation

Applied Inverter

 

minal

 

ening

 

 

 

 

 

 

 

Cable

 

 

 

 

 

Terminal

 

 

 

 

 

 

 

 

Screw

Torque

 

 

 

 

 

mm2

 

AWG

mm2

 

 

 

size

 

 

Nm

 

R, S, T

U, V, W

R, S, T

U, V, W

R, S, T

U, V, W

R, S, T

U, V, W

FR-S520E-0.1K

 

M3.5

 

1.2

 

2-3.5

2-3.5

 

2

2

14

 

14

2.5

 

2.5

to 0.75K-NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FR-S520E-

 

 

M4

 

1.5

 

 

2-4

2-4

 

2

2

14

 

14

2.5

 

2.5

1.5K, 2.2K-NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FR-S520E-

 

 

M4

 

1.5

 

5.5-4

5.5-4

 

3.5

3.5

12

 

12

4

 

2.5

3.7K-NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2) Three-phase 400V power input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ter-

 

Tight-

 

 

 

Crimping

 

 

 

Cable

 

PVC Insulation

Applied Inverter

 

minal

 

ening

 

 

 

 

 

 

 

Cable

 

 

 

 

 

Terminal

 

 

 

 

 

 

 

 

Screw

Torque

 

 

 

 

 

mm2

 

AWG

mm2

 

 

 

size

 

 

Nm

 

R, S, T

U, V, W

 

R, S, T

U, V, W

 

R, S, T

U, V, W

R, S, T

U, V, W

FR-S540E-0.4K

 

 

M4

 

1.5

 

 

2-4

2-4

 

2

2

14

 

14

2.5

 

2.5

to 3.7K-NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3) Single-phase 100V power input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Termi-

Tight-

 

Crimping

 

 

Cable

 

PVC Insulation

Applied Inverter

 

 

nal

 

ening

 

 

 

 

Cable

 

 

 

 

Terminal

 

 

 

 

 

 

 

 

 

Screw

Torque

 

 

mm2

 

AWG

mm2

 

 

 

size

 

Nm

 

 

R, S

U, V, W

 

R, S

U, V, W

 

R, S

U, V, W

R, S

 

U, V, W

FR-S510WE-0.1K

 

 

M3.5

 

1.2

 

 

 

2-3.5

 

2-3.5

 

 

2

2

 

14

 

14

2.5

 

2.5

to 0.4K-NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FR-S510WE-0.75K-

 

M4

 

1.5

 

 

 

5.5-4

 

2-4

 

 

3.5

2

 

12

 

14

4

 

2.5

NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

￿Wiring length

100m (328.08 feet) maximum. (50m (164.04 feet) maximum for the FR-S540E- 0.4K-NA.)

CAUTION

When the wiring length of the 0.1K and 0.2K of the three-phase 200V and single-phase 100V class and the 0.4K and 0.75K of the three-phase 400V class is 30m (98.43 feet) or more, set the carrier frequency to 1kHz.

When automatic torque boost is selected in Pr. 98 "automatic torque boost selection (motor capacity)", the wiring length should be 30m (98.43 feet) maximum. (Refer to page 121.)