Mitsubishi Electronics FR-S500 instruction manual

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 27
Image 27
Manual background

Main circuit terminals

1.2.7Regarding the installation of the power factor improving reactor

When the inverter is installed near a large-capacity power transformer (500kVA or more with the wiring length of 10m (32.81feet) or less) or the power capacitor is to be switched, an excessive peak current will flow in the power supply input circuit, damaging the converter circuit. In such a case, always install the power factor improving reactor (FR-BEL(-H) or FR-BAL(-H)).

 

NFB FR-BAL(-H)

Inverter

Power supply equipment

 

 

 

 

R

X

R

U

 

1500

Power factor

Power

S

Y

 

S

V

 

1000

improving reactor

supply

T

Z

capacity (kVA)

installation range

 

T

W

500

 

 

 

P

P1

 

 

 

 

FR-BEL(-H)(*)

0

10

 

 

 

 

Wiring length (m)

REMARKS

 

 

 

 

 

 

 

*When connecting the FR-BEL(-H), remove the jumper across terminals P-P1.

The wiring length between the FR-BEL(-H) and the inverter should be 5m(16.40feet) maximum and as short as possible.

Use the cables which are equal in size to those of the main circuit. (Refer to page 8)

1

WIRING

17

Page 27
Image 27