1.2.10 Power supply harmonics

Main circuit terminals

1.2.10 Power supply harmonics

The inverter may generate power supply harmonics from its converter circuit to affect the power generator, power capacitor etc. Power supply harmonics are different from noise and leakage currents in source, frequency band and transmission path. Take the following countermeasure suppression techniques.

Manual background The following table indicates differences between harmonics and noise:

Item

 

Harmonics

 

 

 

 

Noise

Frequency

Normally 40th to 50th degrees or less

 

High frequency (several 10kHz

(up to 3kHz or less)

 

 

 

 

 

 

 

 

 

to 1GHz order)

 

 

 

 

 

 

 

 

 

 

Environment

To-electric channel, power impedance

To-space, distance, wiring path

Quantitative

Theoretical calculation possible

 

Random occurrence,

understanding

 

quantitative grasping difficult

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Generated amount

Nearly proportional to load capacity

 

Change with current variation

 

ratio (larger as switching speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

increases)

 

 

 

Affected equipment

Specified in standard per equipment

 

Different depending on maker's

immunity

 

equipment specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suppression example

Provide reactor.

 

 

 

 

 

 

 

 

 

Increase distance.

Suppression technique

 

 

 

 

 

 

 

 

 

 

FR-BEL

 

 

 

Harmonic currents produced

 

 

 

 

FR-BAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on the power supply side by

NFB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the inverter change with such

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

conditions as whether there

 

 

 

 

 

 

 

 

 

 

 

 

Inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power factor improving reactor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

are wiring impedances and a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IM

(FR-BEL(-H) or FR-BAL(-H))

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and the magnitudes of output

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not provide power factor

frequency and output current

 

 

 

 

 

 

 

 

 

 

 

 

 

on the load side.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

improving capacitor.

For the output frequency and output current, we understand that they should be calculated in the conditions under the rated load at the maximum operating frequency.

CAUTION

The power factor improving capacitor and surge suppressor on the inverter output side may be overheated or damaged by the harmonic components of the inverter output. Also, since an excessive current flows in the inverter to activate overcurrent protection, do not provide a capacitor and surge suppressor on the inverter output side when the motor is driven by the inverter. To improve the power factor, insert a power factor improving reactor on the inverter's primary side or DC circuit. For full information, refer to page 17.

20