2.5.2Zero current detection (Pr. 50 , Pr. 51 )

Current detection function parameters

2.5.2Zero current detection (Pr. 50 Manual background, Pr. 51 Manual background)

When the inverter's output current falls

Start signal

OFF

ON

Pr.50

 

 

 

 

 

to "0[A]", torque will not be generated. This may cause a gravity drop when the inverter is used in vertical lift application.

Output current 0 [A] Zero current detection signal output (Y13)

 

 

 

 

"zero

Pr.50

 

 

 

current

 

100ms

 

detection

 

 

 

OFF

ON

OFF

ON

level"

 

Pr.51

Pr.51

 

 

detection period detection period

To prevent this, the output current "zero" signal can be output from the inverter to close the mechanical brake when the output current has fallen to "0[A]".

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

50

Zero current detection level

5%

0 to 200%

Setting is enabled when

 

 

 

 

Pr. 30 = "1"

51

Zero current detection period

0.5s

0.05 to 1s

POINT

If the output is lower than the Pr. 50 setting for longer than the time set in Pr. 51 during inverter operation, the zero current detection (Y13) signal is output from the inverter's open collector output terminal or contact output terminal.

<Setting>

Parameter

Description

Set the zero current detection level.

50Set the level of zero current detection in terms of the percentage of the rated inverter current from the output current value of 0 [A].

Set the zero current detection period.

51Set a period of time from when the output current falls to or below the Pr. 50 setting to when the zero current detection signal (Y13) is output.

Use Pr. 64 or Pr. 65 (output terminal function selection) to assign the terminal used for Y13 signal output.

CAUTION

If the current falls below the preset detection level but the timing condition is not satisfied, the zero current detection signal is held on for about 100ms.

When the terminal functions are changed using Pr. 64, Pr. 65, the other functions may be affected. Please make setting after confirming the function of each terminal.

When running (connecting) multiple motors with one inverter in due order, the zero current detection signal (Y13) may be output. Set 13% or more for the 0.1K and 8% or more for the 0.2K.

(when the total capacity of motors is less than the zero current detection level and the motor capacity per inverter is less than the zero current detection level)

Related parameters

Assignment of Y13 signal to terminal ⇒ Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C terminal function selection" (refer to page 100)