Mitsubishi Electronics FR-S500 Clear parameters, Parameter clear CLr, Alarm history clear ECL

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 139
Image 139

Clear parameters

2.14 Clear parameters

2.14.1 Parameter clear (CLr )

Initializes the parameter values to the factory settings.

Clear the parameters during a stop in the PU operation mode.

Parameter

Name

Factory

Setting

Remarks

 

Setting

Range

 

 

 

 

 

 

 

 

 

0: Clear is not executed.

 

 

 

 

 

1: Parameter clear *1

 

 

 

 

 

(Calibration parameters C1 to

Setting is

CLr

Parameter

0

0, 1, 10

C7 are not cleared)

enabled

clear

10: All clear *2

when Pr. 30

 

 

 

 

(All settings including those of

= "1"

 

 

 

 

the calibration parameters C1

 

 

 

 

 

to C7 return to factory settings)

 

*1.Parameters are not cleared by setting "1" in Pr. 77 "parameter write disable selection".

Pr. 75, Pr. 38, Pr. 39, Pr. 53, Pr. 60 to Pr. 65, Pr. 99, maintenance parameters H1, H2, calibration parameters C1 to C7 and communication parameters n13, n15 are not cleared.

*2.Pr. 75, maintenance parameter H1 and communication parameter n13 are not cleared.

REMARKS

For details of the operation procedure, refer to the instruction manual (basic).

2.14.2 Alarm history clear (ECL )

Clear the alarm history.

Parameter

Name

Factory

Setting

 

Remarks

Setting

Range

 

 

 

 

 

 

ECL

Alarm history

0

0, 1

0: Not cleared

 

Setting is enabled

clear

1: Alarm history clear

when Pr. 30 = "1"

 

 

 