Errors (Alarms)

3.1.1Error (alarm) definitions

(1) Major failures

When the protective function is activated, the inverter output is shut off and the alarm is output.

Operation Panel Indication

OC1

 

 

FR-PU04

OC During Acc

 

 

 

 

 

Name

Overcurrent shut-off during acceleration

 

 

When the inverter output current reaches or exceeds

Description

approximately 200% of the rated inverter current during

acceleration, the protective circuit is activated to stop the inverter

 

 

output.

 

 

 

Check for sudden acceleration.

 

 

Check point

Check that the downward acceleration time is not long in vertical

lift application.

 

 

 

 

 

 

Check for output short-circuit/ground fault.

 

Corrective action

Increase the acceleration time.

 

 

Shorten the downward acceleration time in vertical lift application.

 

Operation Panel Indication

OC2

 

 

FR-PU04

Stedy Spd OC

 

 

 

 

 

Name

Overcurrent shut-off during constant speed

 

 

When the inverter output current reaches or exceeds

Description

approximately 200% of the rated inverter current during constant-

speed operation, the protective circuit is activated to stop the

 

 

inverter output.

 

 

Check point

Check for sudden load change.

 

 

Check for output short-circuit/ground fault.

 

 

 

Corrective action

Keep load stable.

 

 

Operation Panel Indication

OC3

 

 

FR-PU04

OC During Dec

 

 

 

 

 

Name

Overcurrent shut-off during deceleration

 

 

When the inverter output current reaches or exceeds

Description

approximately 200% of the rated inverter current during

deceleration (other than acceleration or constant speed), the

 

 

protective circuit is activated to stop the inverter output.

Check point

Check for sudden speed reduction.

 

Check for output short-circuit/ground fault.

 

 

Check for too fast operation of motor's mechanical brake.

Corrective action

Increase the deceleration time.

 

 

Adjust brake operation.

 

 

 

 

 

PROTECTIVE FUNCTIONS

3

157

Page 167
Image 167
Mitsubishi Electronics FR-S500 Error alarm definitions, Major failures, OC During Acc, Stedy Spd OC, OC During Dec