(3) Warnings

Errors (Alarms)

(3) Warnings

Operation Panel Indication

OL

 

FR-PU04

 

OL

 

 

 

 

 

 

Name

Stall prevention

(overcurrent)

 

 

 

 

 

If a current of more than 150% (* 3) of the rated

 

 

inverter current flows in the motor, this function

 

During

stops the increase in frequency until the overload

 

current reduces to prevent the inverter from

 

acceleration

 

resulting in overcurrent shut-off. When the overload

 

 

 

 

current has reduced below 150%, this function

 

 

increases the frequency again.

 

 

 

If a current of more than 150% (* 3) of the rated

 

During

inverter current flows in the motor, this function

 

lowers the frequency until the overload current

Description

constant-

reduces to prevent overcurrent shut-off. When the

speed

 

overload current has reduced below 150%, this

 

operation

 

function increases the frequency up to the set

 

 

 

 

value.

 

 

 

If a current of more than 150% (* 3) of the rated

 

 

inverter current flows in the motor, this function

 

During

stops the decrease in frequency until the overload

 

current reduces to prevent the inverter from

 

deceleration

 

resulting in overcurrent shut-off. When the overload

 

 

 

 

current has reduced below 150%, this function

 

 

decreases the frequency again.

 

Check point

Check the motor for use under overload.

 

 

• The acceleration/deceleration time may change.

 

 

• Increase the stall prevention operation level with Pr. 22 "stall

Corrective action

prevention operation level", or disable stall prevention with Pr. 21

"stall prevention function selection".

 

 

 

 

• Check that the torque boost (Pr. 0) setting is not higher than

 

required.

 

 

 

 

*3. The stall prevention operation current can be set as desired. It is factory-set to 150%.

Operation Panel Indication

oL

 

FR-PU04

oL

 

 

 

 

 

Name

Stall prevention

(overvoltage)

 

 

 

 

If the regenerative energy of the motor increases

Description

During

too much to exceed the brake capability, this

function stops the decrease in frequency to prevent

deceleration

 

overvoltage shut-off. As soon as the regenerative

 

 

 

 

energy has reduced, deceleration resumes.

Check point

Check for sudden speed reduction.

 

Corrective action

The deceleration time may change. Increase the deceleration time

using Pr. 8 "deceleration time".

 

 

 