Communication parameters

<Setting>

To make communication between the personal computer and inverter, initialization of the communication specifications must be made to the inverter. If initial setting is not made or there is a setting fault, data transfer cannot be made.

*After making the initial setting of the parameters, always reset the inverter. After you have changed the communication-related parameters, communication cannot be made until the inverter is reset.

Parameter

Description

Setting

Description

 

Communication

 

 

 

Station number specified for communication from

n1

0 to 31

the RS-485 connector.

station number

Set the inverter station numbers when two or more

 

 

 

 

 

 

 

 

 

inverters are connected to one personal computer.

 

Communication

48

 

4800bps

n2

96

 

9600bps

speed

 

 

192

 

19200bps

 

 

 

 

 

8 bits

 

0

Stop bit length 1 bit

n3

Stop bit length/

 

1

Stop bit length 2 bits

 

 

data length

 

 

 

 

7 bits

 

10

Stop bit length 1 bit

 

 

 

 

 

11

Stop bit length 2 bits

 

Parity check

0

 

 

Absent

n4

presence/

1

 

 

Odd parity present

 

absence

2

 

 

Even parity present

 

 

 

 

 

Set the permissible number of retries at occurrence

 

 

 

 

 

of a data receive error.

 

 

0 to 10

If the number of consecutive errors exceeds the

 

 

 

 

 

permissible value, the inverter will come to an alarm

 

Number of

 

 

 

stop (OPT).

 

 

 

 

If a communication error occurs, the inverter will not

n5

communication

 

 

 

 

 

 

come to an alarm stop. At this time, the inverter can

 

retries

 

 

 

 

---

 

be coasted to a stop by MRS or RES input.

 

 

 

 

 

 

During a communication error (H0 to H5), the minor

 

 

(65535)

 

 

fault signal (LF) is switched on. Allocate the used

 

 

 

 

 

 

 

 

 

 

terminal with any of Pr. 64, Pr. 65 (output terminal

 

 

 

 

 

function selection).

 

 

0

 

 

No communication

 

Communication

 

 

 

Set the communication check time [s] interval.

 

 

 

 

If a no-communication state persists for longer than

n6

check time

0.1 to 999

the permissible time, the inverter will come to an

 

interval

 

 

 

alarm stop (OPT).

 

 

 

 

 

 

 

---

 

Communication check suspension.

 

Waiting time

0 to 150

Set the waiting time between data transmission to

n7

the inverter and response.

setting

 

 

 

 

---

 

Set with communication data.

 

 

 

n11

CR/LF selection

0

 

 

Without CR/LF

1

 

 

With CR, without LF

 

 

2

 

 

With CR/LF

2

FUNCTIONS

133

Page 143
Image 143
Mitsubishi Electronics FR-S500 instruction manual 133