2.3.19 Start-time ground fault detection selection (Pr. 40 )

Output terminal function parameters

2.3.19 Start-time ground fault detection selection (Pr. 40 2.4 Output terminal function parameters)

You can choose whether to make ground fault detection at start valid or invalid. Ground fault detection is executed only right after the start signal is input to the inverter.

Protective function will not activate if a ground fault occurs during operation.

Parameter

Name

Factory

Setting

Remarks

 

Setting

Range

 

 

 

 

 

 

Start-time ground

 

 

0: Ground fault detection for

Setting is

40

0

0, 1

protection is not executed.

fault detection

1: Ground fault detection for

enabled when

 

selection

 

 

Pr. 30 = "1".

 

 

 

 

protection is executed.

 

CAUTION

1.If a ground fault is detected with "1" set in Pr. 40, alarm output " 2.4.1Up-to-frequency (Pr. 41Manual backgroundManual background" is detected and the output is shut off.

2.If the motor capacity is less than 0.1kW, ground fault protection may not be provided.

REMARKS

When a ground fault is detected with "1" set in Pr. 40, an approximate 20ms delay occurs at every start.

2.4 Output terminal function parameters

2.4.1

Up-to-frequency (Pr. 41

)

 

 

 

The ON range of the up-to-

 

 

 

Running

Adjustable

frequency signal (SU) output

 

 

(Hz)

frequency

range Pr.41

when the output frequency

 

 

 

 

 

 

reaches the running frequency

 

 

 

 

 

Output frequency

 

 

can be adjusted between 0 and

 

 

 

±100% of the running frequency.

 

 

 

This parameter can be used to

 

 

 

ensure that the running

 

 

Time

 

 

 

 

frequency has been reached to

Output signal

OFF

ON

OFF

provide the operation start

signal etc. for related

(SU)

 

 

ON

OFF

equipment.

Start signal

 

 

 

 

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

41

Up-to-frequency

10%

0 to 100%

Setting is enabled when Pr. 30 = "1".

Use Pr. 64 or Pr. 65 (output terminal function selection) to assign the terminal used for SU signal output.

CAUTION

Using Pr. 64 or Pr. 65 to change the terminal assignment may affect the other functions. Please make setting after confirming the function of each terminal. (Refer to page 100.)

Related parameters

Assignment of SU signal to terminal ⇒ Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C terminal function selection" (refer to page 100)