Changeover contact output indicates

Manual background Standardconnection diagramand terminal specifications

 

Symbol

Terminal Name

Definition

 

 

 

 

 

 

 

Changeover contact output indicates

 

 

 

 

 

A

 

that the inverter protective function has

 

 

 

 

 

 

activated and the output stopped.

 

 

 

 

 

B

Alarm output

230VAC 0.3A, 30VDC 0.3A. Alarm:

 

 

 

 

 

C

 

discontinuity across B-C (continuity

The function of the

 

 

 

 

 

 

across A-C), Normal: continuity across

terminals changes

 

 

 

 

 

 

B-C (discontinuity across A-C).(*5)

according to the

 

 

Open collector

 

 

 

Switched low when the inverter output

output terminal

 

 

 

 

 

frequency is equal to or higher than the

function selection

 

 

 

 

Inverter

starting frequency (factory set to 0.5Hz

(Pr. 64, Pr.65).

signals

 

 

RUN

variable). Switched high during stop or

(*4)

 

 

 

running

DC injection brake operation. (*2)

 

 

 

 

 

Permissible load 24VDC 0.1A (a

 

 

 

 

 

voltage drop is 3.4V maximum when

 

 

 

 

 

the signal is on)

 

Output

 

 

 

 

 

 

 

 

SE

Open collector

Common terminal for inverter running terminal RUN. (*6)

 

 

common

 

 

Indicator

 

 

 

The output signal across terminals AM-5 is factory set to about

 

 

 

AM

Analog signal

5VDC at 60Hz and is proportional to the corresponding output

 

 

 

frequency.

 

 

 

 

 

output

Frequency permissible load current 1mA

 

 

 

 

 

 

 

 

 

 

Output signal 0 to 5VDC

 

 

 

 

 

 

 

 

Communication

 

 

 

 

RS-485

Using the parameter unit connection cable (FR-CB201 to

 

 

——

205), the parameter unit (FR-PU04) can be connected.

 

 

connector

Communication operation can be performed using RS-485.

 

 

 

 

 

 

 

 

 

For details of RS-485 communication, refer to page 42.

 

 

 

 

 

 

 

*1. Do not connect terminals SD and PC each other or to the ground.

For sink logic (factory setting), terminal SD acts as the common terminal of contact input. For source logic, terminal PC acts as the common terminal of contact input. (Refer to page 23 for switching method.)

*2. Low indicates that the open collector output transistor is on (conducts). High indicates that the transistor is off (does not conduct).

*3. RL, RM, RH, RT, AU, STOP, MRS, OH, REX, JOG, RES, X14, X16, (STR) signal selection (Refer to page 98.)

*4. RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL, Y93, Y95, LF, ABC signal selection (Refer to page 100.)

*5. To be compliant with the European Directive (Low Voltage Directive), the operating capacity of relay outputs (A, B, C) should be 30VDC 0.3A.

*6. Terminals SD, SE and 5 are isolated from each other. Do not ground.