Mitsubishi Electronics FR-S500 instruction manual Current detection function parameters, Setting

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 98
Image 98
2.5 Current detection function parameters

Current detection function parameters

2.5 Current detection function parameters

2.5.1Output current detection functions (Pr. 48 2.5.1Output current detection functions (Pr. 48 , Pr. 49 ), Pr. 49 Manual background)

If the output remains higher than the Pr. 48 setting during inverter operation for longer than the time set in Pr. 49, the output current detection signal (Y12) is output from the inverter's open collector output or contact output terminal.

Output current detection

signal (Y12) OFF

currentOutput

 

Pr.48

 

 

 

 

 

 

100ms

ON OFF

Pr.49

Time

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

48

Output current

150%

0 to 200%

 

detection level

Setting is enabled when

 

 

 

 

 

 

 

Pr. 30 = "1"

49

Output current

0s

0 to 10s

detection period

 

 

 

 

 

<Setting>

Parameter

Description

Number

 

48Set the output current detection level.

100% is the rated inverter current.

Set the output current detection period. Set the time from when the output

49current has risen above the Pr. 48 setting until the output current detection signal (Y12) is output.

Use Pr. 64 or Pr. 65 (output terminal function selection) to assign the terminal used for Y12 signal output.

CAUTION

Once turned ON, when the output current has risen above the preset detection level, the output current detection signal is held for at least 100ms (approximately).

Using Pr. 64 or Pr. 65 (output terminal function selection) to change terminal assignment may affect the other functions. Make setting after confirming the function of each terminal.

Related parameters

Assignment of Y12 signal to terminal ⇒ Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C terminal function selection" (refer to page 100)

88

Page 98
Image 98
Mitsubishi Electronics FR-S500 Current detection function parameters, Output current detection functions Pr. 48 , Pr