Mitsubishi Electronics FR-S500 instruction manual Grounding precautions

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 29
Image 29
1.2.9Grounding precautions

Main circuit terminals

1.2.9Grounding precautions

￿Leakage currents flow in the inverter. To prevent an electric shock, the inverter and motor must be grounded. Grounding must conform to the requirements of national and local safety regulations and electrical codes.

(JIS, NEC section 250, IEC 536 class 1 and other applicable standards)

￿Use the dedicated ground terminal to ground the inverter. (Do not use the screw in the casing, chassis, etc.)

Use a tinned* crimping terminal to connect the ground cable. When tightening the screw, be careful not to damage the threads.

*Plating should not include zinc.

￿Use the thickest possible ground cable. Use the cable whose size is equal to or greater than that indicated in the following table, and minimize the cable length. The grounding point should be as near as possible to the inverter.

Motor Capacity

Ground Cable Size (Unit: mm2)

200V class, 100V class

400V class

 

2.2kW or less

2 (2.5)

2 (2.5)

3.7kW

3.5 (4)

2 (4)

For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated within parentheses.

￿ Ground the motor on the inverter side using one wire of the 4-core cable.

1

WIRING

19

Page 29
Image 29
Mitsubishi Electronics FR-S500 instruction manual Grounding precautions