(3) Wiring example

Operation selection function parameters

5)Forward action

Increases the manipulated variable (output frequency) if deviation X = (set point - measured value) is negative, and decreases the manipulated variable if deviation is positive.

[Cooling]

+X>0 Set point•The contact input signal (AU Signal) need not be turned on.

-Manual background X<0

Feedback signal (Measured value)

 

Measured value

Too cold down

Set point

 

Hot up

 

 

Deviation

Relationships between deviation and manipulated variable (output frequency)

 

Deviation

 

Positive

Negative

Reverse action

￿

￿

Forward action

￿

￿

(3) Wiring example

Pr. 60 = 14

 

 

 

 

 

 

 

 

 

Pr. 64 = 15

 

NFB

Inverter

 

Pump

 

 

Pr. 65 = 16

 

R/L1

U

Motor

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

Pr. 88 = 20

 

S/L2

V

IM

 

P

 

 

supply

 

 

 

 

 

 

T/L3

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Forward rotation

 

STF

 

Upper limit

 

For

 

 

 

Reverse rotation

 

STR

 

(Lower limit)

 

 

 

 

 

 

2-wire

 

 

 

 

 

 

Limit signal

For

 

 

 

SD

 

 

type

 

 

PID control

 

 

 

 

3-wire

 

 

RH(X14)(*3)

common

 

Detector

 

 

 

type

 

selection

 

RUN(FUP,FDN)

Forward

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

 

10

(*2)

rotationoutput

-

+

+ -

+

 

potentiometer

 

2

SE

Reverse

 

 

 

 

 

(Set point setting)

 

5

A

rotationoutput

 

 

 

 

 

 

 

 

 

(OUT) (COM) (24V)

 

 

 

 

 

 

 

 

 

 

 

 

C

Forward (reverse)

 

 

 

 

 

 

4

 

rotation output

 

 

 

 

 

 

 

 

signal common

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Measured value) 4 to 20mA

 

 

 

 

 

 

0

24V

 

 

 

 

 

 

 

 

power supply (*1)

 

 

 

 

 

AC1 φ

200/220V 50/60Hz

CAUTION

*1.The power supply must be selected in accordance with the power specifications of the detector used.

*2.The output signal terminals used depends on the Pr. 64, Pr. 65 settings. *3.The input signal terminal used depends on the setting of Pr. 60 to Pr. 63.

The contact input signal (AU Signal) need not be turned on.

2

FUNCTIONS

115

Page 125
Image 125
Mitsubishi Electronics FR-S500 instruction manual Wiring example, The contact input signal AU Signal need not be turned on