Explanation of functions (parameters)

2.3.13 Stall prevention (Pr. 22 , Pr. 23 , Pr. 28 )

Set the output current level (% value to the inverter rated current) at which the output frequency will be adjusted to prevent the inverter from stopping due to overcurrent etc.

During high-speed operation above the rated motor frequency, acceleration may not be made because the motor current does not increase. To improve the operating characteristics of the motor in this case, the stall prevention level can be reduced in the high frequency region. This function is effective for performing operation up to the high speed range on a centrifugal separator etc. Normally, set 60Hz in Pr. 28 "stall prevention operation reduction starting frequency" and 100% in Pr. 23.

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

 

22

Stall prevention operation

150%

0 to 200%



 

level

Setting is

 

 

 

 

 

Stall prevention operation

 

 

 

 

 

0 to 200%,

- - -: Pr. 22

enabled

23

level compensation factor at

- - -

- - -

equally

when

 

double speed

 

 

 

 

 

Pr. 30 = "1".

28

Stall prevention operation

60Hz

0 to 120Hz



 

reduction starting frequency

 

 

 

 

 

 

 

 

 

 

 

 

(%)

 

 

 

 

 

 

 

 

 

compensation factor

 

Setting example

 

 

Pr.22

When Pr.23 ="- - -"

 

 

 

(Pr.22= 150%,

 

 

 

 

 

150

Pr.23=100%, Pr.28=60Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

112.5

 

 

 

 

 

 

 

 

90

 

 

 

 

 

Pr.23

 

 

75

 

preventionStall

operationlevel(%)

 

 

Reductionratio

preventionStall

operationlevel(%)

 

 

 

 

 

 

 

 

Pr.28

120Hz Output

 

 

 

0

6080100120 Output

 

 

 

 

frequency (Hz)

 

 

frequency (Hz)

 

 

 

 

 

 

 

<Setting>

 

 

 

 

 

 

 

Generally, set 150% (factory setting) in Pr. 22 "stall prevention operation level". Setting "0" in Pr. 22 disables stall prevention operation.

To reduce the stall prevention operation level in the high frequency range, set the reduction starting frequency in Pr. 28 "stall prevention operation reduction starting frequency" and the reduction ratio compensation factor in Pr. 23.

Formula for stall prevention operation level

Stall prevention operation level (%) = A + B ×[

Pr. 22-A

 

]×[

Pr. 23-100

]

Pr. 22-B

100

 

 

 

 

 

 

where, A =

Pr. 28 (Hz) × Pr. 22 (%)

, B =

Pr. 28 (Hz) × Pr. 22 (%)

 

output frequency (Hz)

 

120Hz

 

 

 

 

By setting "- - -" (factory setting) in Pr. 23, the stall prevention operation level is constant at the Pr. 22 setting up to 120Hz.

2

FUNCTIONS

77

Page 87
Image 87