How to use the input signals (assigned terminals

RL, RM, RH, STR)

1.5.6 External thermal relay input: Pr. 60 to Pr. 63 setting "7"

When the external thermal relay or thermal relay built in the motor is actuated, the inverter output is shut off and an alarm signal is given to keep the motor stopped to protect the motor from overheat. Even if the thermal relay contact resets, the motor cannot be restarted unless the reset terminals RES-SD are shorted for more than 0.1s and then opened or a power-on reset is made. The function may therefore be used as an external emergency stop signal input.

 

 

Thermal relay

Inverter

 

 

 

 

 

 

 

 

 

Motor

U

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

IM

 

 

 

 

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OH

 

 

 

 

 

 

 

 

 

 

 

 

SD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5.7Jog operation (JOG signal): Pr. 60 to Pr. 63 setting "9"

(1) Jog operation using external signals

Jog operation can be started/stopped by shorting the jog mode select terminals JOG- SD and shorting/opening the start signal terminals STF or STR-SD. The jog frequency and jog acceleration/deceleration time are set in Pr. 15 (factory setting 5Hz, variable between 0 and 120Hz) and Pr. 16 (factory setting 0.5s, variable between 0 and 999s), respectively, and their settings can be changed from the operation panel or parameter unit.

The JOG signal has precedence over the multi-speed signal. (External)

frequency

 

 

Jog frequency Pr. 15

 

 

 

 

Time

 

 

 

Forward

3Hz

DC injection brake

 

 

0.5Hz

rotation

 

 

 

 

 

 

 

 

Output

 

 

 

Reverse

1

 

 

 

rotation

 

 

 

 

 

Across JOG -SD

 

 

 

ON

 

 

 

 

 

 

Forward rotation

 

ON

 

 

WIRING

Across STF-SD

 

 

 

 

 

 

 

 

 

Reverse rotation

 

 

 

ON

 

Across STR-SD

 

 

 

 

 

35