Mitsumi electronic FR-F520-0.75K, 55K instruction manual RT signal activated condition selection Pr

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 147
Image 147

PARAMETERS

4.2.43 RT signal activated condition selection (Pr. 155)

Pr. 155 "RT signal activated condition"

Related parameters

Pr. 14 "load pattern selection" Pr. 44 to Pr. 49

(second function selection) Pr. 180 to Pr. 186

(input terminal function selection)

#Set the condition of activating the RT terminal to select the second control functions by switching on-off the RT signal.

Parameter

Factory

Setting Range

Number

Setting

 

155

0

0, 10

<Setting>

Refer to the following table and set the parameter:

Pr. 155 Setting

Description

0Made valid immediately by switching the RT signal on-off.

Made valid only when the RT signal is on at constant

10speed.

(Invalid during acceleration/deceleration)

4.2.44 Stall prevention function and current limit function (Pr. 156)

Pr. 156 "stall prevention operation selection"

Related parameters

 

Pr. 22 "stall prevention operation level" Pr. 23 "stall prevention operation level compensation factor at double

speed"

Pr. 48 "second stall prevention operation current"

Pr. 49 "second stall prevention operation frequency"

Pr. 154 "voltage reduction selection during stall prevention operation"

Pr. 157 "OL signal output waiting time"

You can make setting to disable stall prevention caused by overcurrent, make setting to disable the fast- response current limit which limits the current to prevent the inverter from resulting in an overcurrent trip if an excessive current occurs due to sudden load variation or ON-OFF, etc. in the output side of the running inverter, and set the OL signal output delay.

Parameter

Factory

Setting Range

Number

Setting

 

156

0

0 to 31, 100, 101

134

Page 147
Image 147
Mitsumi electronic FR-F520-0.75K, 55K RT signal activated condition selection Pr, Pr RT signal activated condition