INSTALLATION AND WIRING

(3) Cables, crimping terminals, etc.

The following table lists the cables and crimping terminals used with the inputs (R, S, T) L1, L2, L3and outputs (U, V, W) of the inverter and the torques for tightening the screws:

FR-F520-0.75K to 55K

Applicable Inverter

 

 

 

 

 

 

Cables (Note 1)

 

PVC insulated

Terminal

Tightening

Crimping Terminals

 

 

 

Cables (Note 1)

 

 

 

 

 

Type

Screw

Torque

 

 

mm2

 

AWG

mm2

 

 

Size

N m

 

 

 

 

 

 

 

 

 

 

R, S, T

U, V, W

R, S, T

 

U, V, W

R, S, T

U, V, W

R, S, T

U, V,

 

 

 

L1, L2, L3

L1, L2, L3

 

L1, L2, L3

L1, L2, L3

W

FR-F520-0.75K to 2.2K

M4

1.5

2-4

2-4

2

 

2

14

14

2.5

2.5

FR-F520-3.7K

M4

1.5

5.5-4

5.5-4

3.5

 

3.5

12

12

4

2.5

FR-F520-5.5K

M5

2.5

5.5-5

5.5-5

5.5

 

5.5

10

10

6

4

FR-F520-7.5K

M5

2.5

14-5

8-5

14

 

8

6

8

16

6

FR-F520-11K

M5

2.5

14-5

14-5

14

 

14

6

6

16

10

FR-F520-15K

M6

4.4

22-6

22-6

22

 

22

4

4

35

16

FR-F520-18.5K

M6

4.4

38-6

38-6

38

 

38

2

2

35

25

FR-F520-22K

M8

7.8

38-8

38-8

38

 

38

2

2

70

35

FR-F520-30K

M8

7.8

60-8

60-8

60

 

60

1/0

1/0

95

50

FR-F520-37K

M10

14.7

100-10

100-10

100

 

100

4/0

4/0

75

70

FR-F520-45K

M10

14.7

100-10

100-10

100

 

100

4/0

4/0

FR-F520-55K

M12

24.5

150-12

150-12

150

 

150

MCM300

MCM300

FR-F540-0.75K to 55K

Applicable Inverter

 

 

 

 

 

 

Cables (Note 1)

 

PVC insulated

 

 

Terminal

Tightening

Crimping Terminals

 

 

 

Cables (Note 1)

 

 

 

 

 

 

 

 

 

Type

Screw

Torque

 

 

mm2

 

AWG

mm2

 

 

 

 

Size

N m

 

 

 

 

 

 

 

 

 

 

 

 

R, S, T

U, V, W

R, S, T

 

U, V, W

R, S, T

U, V, W

R, S, T

U, V,

 

 

 

 

 

L1, L2, L3

L1, L2, L3

 

L1, L2, L3

L1, L2, L3

W

 

 

FR-F540-0.75K to 3.7K

M4

1.5

2-4 2.5-4

2-4 2.5-4

2

 

2

14

14

2.5

2.5

 

 

 

 

 

FR-F540-5.5K

M4

1.5

5.5-4 4-4

2-4 2.5-4

3.5

 

2

12

14

4

2.5

 

 

FR-F540-7.5K

M4

1.5

5.5-4 4-4

5.5-4 4-4

3.5

 

3.5

12

12

4

4

 

2

FR-F540-11K

M4

1.5

5.5-4 4-4

5.5-4 4-4

5.5

 

5.5

10

10

6

6

 

FR-F540-15K

M6

4.4

14-6 16-6

8-6 10-6

14

 

8

6

8

16

10

 

 

FR-F540-18.5K

M6

4.4

14-6 16-6

8-6 10-6

14

 

8

6

8

16

10

 

 

FR-F540-22K

M6

4.4

22-6 25-6

14-6 16-6

22

 

14

4

6

25

16

 

 

FR-F540-30K

M6

4.4

22-6 25-6

22-6 25-6

22

 

22

4

4

25

25

 

 

FR-F540-37K

M6

4.4

22-6 25-6

22-6 25-6

22

 

22

4

4

25

25

 

 

FR-F540-45K

M8

7.8

38-8 50-8

38-8 35-8

38

 

38

2

2

50

35

 

 

FR-F540-55K

M8

7.8

60-8 70-8

60-8 50-8

60

 

60

1/0

1/0

70

50

 

 

Note: 1. The cables used should be 75° C (167° F) copper cables.

2.Tighten the terminal screws to the specified torques. Undertightening can cause a short or misoperation.

Overtightening can cause the screws and unit to be damaged, resulting in a short or misoperation.

(4) Connection of the power supply and motor

Power

R

S

T

U

V

W

L1

L2

L3

supply

 

 

 

 

 

 

 

R

S

T

U

V

W

 

L1〉 〈L2〉 〈 L3

 

 

 

No-fuse breaker

Ground terminal

Ground

Motor

The power supply cables must be connected to R, S, T

L1, L2, L3.

If they are connected to U, V, W, the inverter will be damaged. Phase sequence need not be matched.

For use with a single-phase power supply,the power supply cables must be connected to R and S L1 and L2.

Connect the motor to U, V, W. In the above connection, turning on the forward rotation switch (signal) rotates the motor in the counterclockwise (arrow) direction when viewed from the load shaft.

16