PARAMETERS

When not adjusting the gain voltage go to (5) -1)

When adjusting any point by applying a voltage go to (5) -2)

When adjusting any point without applying a voltage go to (5) -3)

(5) -1) How to adjust the gain frequency only without the voltage being adjusted

#Analog voltage A/D value (%) across terminals 2-5

FR-DU04

CONTROL PANEL

 

Hz

 

A

 

V

MON EXT PU

REV FWD

#Press the

or

key once to display

the current analog voltage adjustment.

Example: When analog voltage

adjustment value is 100%(5V) Press for 1.5 s

SET

Flicker

go to (6)

(5)-2) How to adjust any point by applying a voltage across terminals 2-5 (e.g. from the external potentiometer) (current: across terminals 4-5) (When applying 5V)

#Analog voltage A/D value (%) #Apply a 5V voltage.

across terminals 2-5

 

(Turn the external potentiometer

FR-DU04

CONTROL PANEL

 

connected across terminals 2-5 to maximum.)

 

 

Hz

 

 

 

 

 

 

 

 

A

 

 

 

 

V

 

 

MON

EXT

PU

 

 

 

REV

FWD

 

 

Press for 1.5 s

SET

Flicker

When the potentiometer is at the maximum position, the value is nearly 100.

go to (6)

(5)-3) How to adjust any point without applying a voltage across terminals 2-5 (without a current flowing across terminals 4-5) (when changing from 4V (80%) to 5V (100%))

 

 

 

 

 

 

 

 

#Set the gain voltage (%) with

 

 

 

#Press the

or

key

the

/

key.

# Analog voltage A/D value (%)

 

once to display the current

[0(%) for 0V (0mA), 100(%) for

across terminals 2-5

 

analog voltage calibration value.

5V (10V, 20mA)]

FR-DU04

 

Hz

/

 

 

 

 

 

 

 

CONTROL PANEL

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

V

 

 

 

 

 

 

 

 

Press for 1.5 s

 

 

 

 

 

 

 

 

 

 

MON

EXT

PU

 

 

 

 

 

 

 

 

 

REV

FWD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SET

 

 

 

 

 

 

 

Flicker

 

go to (6)

 

 

 

 

 

 

 

 

(6)Press the SET key to shift to the next parameter.

(7)Re-set Pr. 79 "operation mode selection" according to the operation mode to be used.