4.2.56Frequency setting voltage (current) bias and gain (Pr. 902 to Pr. 905)

Pr. 902 "frequency setting voltage bias" Pr. 903 "frequency setting voltage gain" Pr. 904 "frequency setting current bias" Pr. 905 "frequency setting current gain"

Related parameters

Pr. 20 "acceleration/deceleration reference frequency"

Pr. 73 "0-5V/0-10V selection"

Pr. 79 "operation mode selection"

You can set the output frequency as desired in relation to the frequency setting signal (0 to 5V, 0 to 10V or 4 to 20mA DC).

The "bias" and "gain" functions are used to adjust the relationship between the input signal entered from outside the inverter to set the output frequency, e.g. 0 to 5VDC, 0 to 10VDC or 4 to 20mADC, and the output frequency.

#Use Pr. 902 to set the bias frequency at 0V.

#Use Pr. 903 to set the output frequency relative to the frequency command voltage set in Pr. 73.

#Use Pr. 904 to set the bias frequency at 4mA.

#Use Pr. 905 to set the output frequency relative to the 20mA frequency command current (4 to 20mA).

Parameter

Factory Setting

Setting Range

Number

 

 

 

 

902

0V

0Hz

0 to 10V

0 to 60Hz

903

5V

60Hz 50Hz

0 to 10V

1 to 120Hz

904

4mA

0Hz

0 to 20mA

0 to 60Hz

905

20mA

60Hz 50Hz

0 to 20mA

1 to 120Hz

(Hz)

60Hz

frequencyOutput

50Hz

 

 

 

 

 

 

 

 

 

 

Bias

 

Pr.902

 

Pr.904

 

 

 

 

 

 

0

0

0

4

Factory setting

Gain Pr.903

Pr.905

4

100% Pr.73

Frequency setting signal 5V

10V

20mA

<Setting>

(1)The frequency setting voltage biases and gains may be adjusted in either of the following three ways:

1)Any point can be adjusted with a voltage applied across terminals 2-5.

2)Any point can be adjusted with no voltage applied across terminals 2-5.

3)Bias voltage is not adjusted.

(2)The frequency setting current biases and gains may be adjusted in either of the following three ways:

1)Any point can be adjusted with a current flowing at terminal 4.

2)Any point can be adjusted with no current flowing at terminal 4.

3)Bias current is not adjusted.