PROTECTIVE FUNCTIONS

(2) Minor fault

When the protective function is activated, the output is not shut off. You can make parameter setting to output the light fault signal. (Set "98" in any of Pr. 190 to Pr. 195 (output terminal function selection). Refer to page 140)

Operation Panel

FN

 

FR-PU04

 

Fan Failure

Indication

 

 

 

 

 

 

 

Name

Fan fault

 

 

 

 

For the inverter which contains a cooling fan, FN appears on the operation panel

Description

when the cooling fan stops due to a fault or operates differently from the setting

 

of Pr. 244 "cooling fan operation selection".

 

Check point

Check the cooling fan for a fault.

 

Corrective action

Change the fan.

 

 

 

(3) Warnings

Operation Panel

OL

 

 

FR-PU04

 

OL

Indication

 

 

 

 

 

 

 

 

 

Name

Stall prevention (Over current)

 

 

 

 

If a current of more than 120% (Note 5) of the rated inverter

 

 

 

current flows in the motor, this function stops the increase in

 

During

frequency until the overload current reduces to prevent the

 

acceleration

inverter from resulting in overcurrent shut-off. When the

 

 

 

overload current has reduced below 120%, this function

 

 

 

increases the frequency again.

 

 

 

 

If a current of more than 120% (Note 5) of the rated inverter

 

 

 

current flows in the motor, this function lowers the frequency

Description

During constant-

until the overload current reduces to prevent overcurrent

speed operation

shut-off. When the overload current has reduced below

 

 

 

 

120%, this function increases the frequency up to the set

 

 

 

value.

 

 

 

 

If a current of more than 120% (Note 5) of the rated inverter

 

 

 

current flows in the motor, this function stops the decrease in

 

During

frequency until the overload current reduces to prevent the

 

deceleration

inverter from resulting in overcurrent shut-off. When the

 

 

 

overload current has reduced below 120%, this function

 

 

 

decreases the frequency again.

 

Check point

Check the motor for use under overload.

 

 

The acceleration/deceleration time may change. Increase the stall prevention

Corrective action

operation level with Pr. 22 "stall prevention operation level" or disable stall

 

prevention with Pr. 156 "stall prevention operation selection".