PROTECTIVE FUNCTIONS

5.1.4 Alarm code output

By setting Pr. 76 "alarm code output selection", an alarm definition can be output as a 4-bit digital signal. This signal is output from the open collector output terminals equipped as standard on the inverter.

Correlations between alarm definitions and alarm codes are as follows.

Operation Panel

 

Output Terminal Signal On-Off

 

 

 

Display

SU

 

IPF

OL

 

FU

Alarm Code

Alarm Output (across B-C)

(FR-DU04)

 

 

 

 

 

 

 

 

 

 

 

 

E.OC1

0

 

0

0

 

1

1

 

E.OC2

0

 

0

1

 

0

2

Provided (Open)

E.OC3

0

 

0

1

 

1

3

 

E.OV1

 

 

 

 

 

 

 

 

E.OV2

0

 

1

0

 

0

4

Provided (Open)

E.OV3

 

 

 

 

 

 

 

 

E.THM

0

 

1

0

 

1

5

Provided (Open)

E.THT

0

 

1

1

 

0

6

 

 

 

E.IPF

0

 

1

1

 

1

7

Provided (Open)

E.UVT

1

 

0

0

 

0

8

Provided (Open)

E.FIN

1

 

0

0

 

1

9

Provided (Open)

E. GF

1

 

0

1

 

1

B

Provided (Open)

E.OHT

1

 

1

0

 

0

C

Provided (Open)

E.OLT

1

 

1

0

 

1

D

Not provided (Closed) (Provided

 

 

when OLT is displayed (Open))

 

 

 

 

 

 

 

 

E.OPT

1

 

1

1

 

0

E

Provided (Open)

E.OP1 to E.OP3

1

 

1

1

 

0

E

Provided (Open)

E. PE

 

 

 

 

 

 

 

Provided (Open)

E.PUE

 

 

 

 

 

 

 

Provided (Open)

E.RET

 

 

 

 

 

 

 

Provided (Open)

E.LF

1

 

1

1

 

1

F

Provided (Open)

E.CPU

 

 

 

 

 

 

 

Provided (Open)

E. 6

 

 

 

 

 

 

 

Provided (Open)

E. 7

 

 

 

 

 

 

 

Provided (Open)

(Note) 0: Output transistor OFF, 1: Output transistor ON (common terminal SE) The alarm output assumes that Pr. 195 setting is "99" (factory setting).

5.1.5 Resetting the inverter

The inverter can be reset by performing any of the following operations. Note that the electronic overcurrent protection's internal heat calculation value and the number of retries are cleared (erased) by resetting the inverter.

Operation 1: Using the operation panel (FR-DU04), press the

Operation 2: Switch power off once, then switch it on again.

Operation 3: Switch on the reset signal (RES).

STOP

key to reset the inverter.

RESET

173

Page 187
Image 187
Mitsumi electronic FR-F520-0.75K, 55K Alarm code output, Resetting the inverter, Key to reset the inverter