Mitsumi electronic FR-F520-0.75K, 55K Set Pr to Pr and Pr in accordance with the following table

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 99
Image 99

PARAMETERS

4.2.22Monitor display / FM, AM terminal function selection (Pr. 52 to Pr. 54, Pr. 158)

Pr. 52 "DU/PU main display data selection" Pr. 53 "PU level display data selection" Pr. 54 "FM terminal function selection"

Pr. 158 "AM terminal function selection"

Related parameters

Pr. 37 "speed display"

Pr. 55 "frequency monitoring reference" Pr. 56 "current monitoring reference" Pr. 170 "watt-hour meter clear"

Pr. 171 "actual operation hour meter clear"

Pr. 900 "FM terminal calibration" Pr. 901 "AM terminal calibration"

You can select the signals shown on the operation panel (FR-DU04)/parameter unit (FR-PU04) main display screen and on the parameter unit (FR-PU04) level meter and signals output to the FM and AM terminals.

#There are two different signal outputs: FM pulse train output terminal and AM analog output terminal. Select the signals using Pr. 54 and Pr. 158.

Parameter Number

Factory Setting

Setting Range

52

0

0, 5, 6, 8, 10 to 14, 17, 20, 23, 24, 25, 100

53

1

0 to 3, 5, 6, 8, 10 to 14, 17

54

1

1 to 3, 5, 6, 8, 10 to 14, 17, 21

158

1

1 to 3, 5, 6, 8, 10 to 14, 17, 21

<Setting>

Set Pr. 52 to Pr. 54 and Pr. 158 in accordance with the following table:

 

 

 

 

 

 

 

Parameter Setting

 

 

 

 

Display

 

 

Pr.52

 

 

Pr.53

Pr.54

Pr.158

Full-Scale Value of

 

Signal Type

 

 

 

 

PU

 

 

 

 

 

Unit

 

DU

 

 

 

PU level

FM

AM

FM, AM, Level Meter

 

 

 

 

 

main

 

 

 

 

 

LED

 

 

 

meter

terminal

terminal

 

 

 

 

 

 

monitor

 

 

 

 

 

 

 

 

 

 

 

 

No display



 

 

 

 

0



 

Output frequency

Hz

 

0/100

 

 

0/100

 

1

1

1

Pr. 55

 

Output current

A

 

0/100

 

 

0/100

 

2

2

2

Pr. 56

 

Output voltage

V

 

0/100

 

 

0/100

 

3

3

3

400V or 800V

 

Alarm display



 

0/100

 

 

0/100

 



 

Frequency setting

Hz

 

5

 

 

*

 

5

5

5

Pr. 55

 

Running speed

r/min

 

6

 

 

*

 

6

6

6

Pr. 55 value converted into Pr. 37

 

 

 

 

value

 

 

 

 

 

 

 

 

 

 

 

 

 

Converter output voltage

V

 

8

 

 

*

 

8

8

8

400V or 800V

 

Regenerative brake duty

%

 

 

 

*

 



 

Electronic overcurrent

%

 

10

 

 

*

 

10

10

10

Protection operation level

 

protection load factor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output current peak value

A

 

11

 

 

*

 

11

11

11

Pr. 56

 

Converter output voltage

V

 

12

 

 

*

 

12

12

12

400V or 800V

 

peak value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input power

kW

 

13

 

 

*

 

13

13

13

Rated power of inverter rating

2

Output power

kW

 

14

 

 

*

 

14

14

14

Rated power of inverter rating

2

Input terminal status



 

 

 

*

 



 

Output terminal status



 

 

 

*

 



 

Load meter **

%

 

17

 

 

17

 

17

17

17

Pr. 56

 

Cumulative operation time

h

 

20

 

 

20

 



 

 

 

 

 

 

 

 

 

 

 

 

1440Hz is output to FM terminal.

Reference voltage output



 

 

 

 

21

21

Full-scale voltage is output to AM

 

 

 

 

 

 

 

 

 

 

 

terminal.

 

Actual operation time

h

 

23

 

 

23

 



 

Motor load factor

%

 

24

 

 

24

 

Rated inverter current 2

 

Cumulative power

kW

 

25

 

 

25

 



 

86

Page 99
Image 99
Mitsumi electronic FR-F520-0.75K, 55K instruction manual Set Pr to Pr and Pr in accordance with the following table