PARAMETERS

4.2.32 Input filter time constant (Pr. 74)

Pr. 74 "filter time constant"

You can set the input section's internal filter constant for an external voltage or current frequency setting signal.

#Effective for eliminating noise in the frequency setting circuit.

#Increase the filter time constant if steady operation cannot be performed due to noise. A larger setting results in lower response. (The time constant can be set between approximately 1ms to 1s. with the setting of 0 to 8. A larger setting results in a larger filter time constant.)

Parameter

Factory

Setting Range

Number

Setting

 

74

1

0 to 8

4.2.33 Reset selection/disconnection PU detection/PU stop selection (Pr. 75)

Pr. 75 "reset selection/disconnection PU detection/PU stop selection"

You can select the reset input acceptance, PU (FR-DU04/FR-PU04) connector disconnection detection

function and PU stop function.

 

 

 

 

 

Reset selection

 

: You can select the reset function input timing.

PU disconnection detection

: When it is detected that the PU (FR-DU04/FR-PU04) is

 

 

 

 

 

disconnected from the inverter for more than 1 second, the inverter outputs

 

 

 

 

 

an alarm code (E.PUE) and comes to an alarm stop.

PU stop selection

 

: When an alarm occurs in any operation mode, you can stop the motor from

 

 

 

 

 

the PU by pressing the

STOP

key.

 

 

 

 

 

RESET

 

 

 

 

 

 

 

 

 

 

Parameter

 

Factory

 

Setting Range

 

 

 

 

Number

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

75

 

14

 

0 to 3, 14 to 17

 

 

 

<Setting>

Pr. 75

Reset Selection

PU Disconnection Detection

PU Stop Selection

Setting

 

 

 

 

 

 

 

 

 

 

 

0

Reset input normally enabled.

If the PU is disconnected, operation

 

 

 

 

Reset input enabled only when the

Pressing the

STOP

key

1

will be continued.

protective function is activated.

RESET

 

 

decelerates the motor to a stop only in

2

Reset input normally enabled.

When the PU is disconnected, the

 

 

 

 

Reset input enabled only when the

the PU operation mode.

 

3

inverter output is shut off.

 

protective function is activated.

 

 

 

 

 

 

 

 

14

Reset input normally enabled.

If the PU is disconnected, operation

 

 

 

 

Reset input enabled only when the

 

 

 

15

will be continued.

 

STOP

 

protective function is activated.

Pressing the

key

 

 

RESET

 

 

 

decelerates the motor to a stop in any

16

Reset input normally enabled.

When the PU is disconnected, the

of the PU, external and

 

 

 

 

 

 

 

 

 

 

 

inverter output is shut off.

communication operation modes.

17Reset input enabled only when the protective function is activated.

100

Page 113
Image 113
Mitsumi electronic FR-F520-0.75K, 55K instruction manual Input filter time constant Pr, Pr filter time constant