Mitsumi electronic FR-F520-0.75K, 55K Insulation resistance test using megger, Pressure test

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 191
Image 191

PROTECTIVE FUNCTIONS

5.3.4Insulation resistance test using megger

1)Before performing the insulation resistance test using a megger on the external circuit, disconnect the cables from all terminals of the inverter so that the test voltage is not applied to the inverter.

2)For the continuity test of the control circuit, use a meter (high resistance range) and do not use the megger or buzzer.

3)For the inverter, conduct the insulation resistance test on the main circuit only as shown below and do not perform the test on the control circuit. (Use a 500VDC megger.)

 

R L1Inverter

U

Motor

Power

 

IM

S L2

V

 

 

 

 

supply

 

 

 

 

T L3

W

 

 

 

 

 

DC500V megger

Ground terminal

5.3.5 Pressure test

Do not conduct a pressure test. The inverter's main circuit uses semiconductors, which may be deteriorated if a pressure test is made.

5.3.6 Daily and Periodic Inspection

Area of

 

 

 

Interval

 

 

 

 

Inspection

 

 

Periodic

 

 

 

Inspec-

Description

 

Method

Criterion

Instrument

Item

Daily

1

2

tion

 

 

 

 

 

 

 

year

years

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient

 

 

 

 

 

 

 

 

temperature:

 

 

 

 

 

 

 

 

(constant torque)

 

 

 

 

 

 

 

 

10ºC to +50ºC

 

 

 

Check ambient

 

 

 

 

(14ºF to 122ºF),

Thermometer,

 

Surrounding

$

 

 

(Refer to page 7)

non-freezing.

 

environment

temperature, humidity,

 

 

(Variable torque)

hygrometer,

 

dust, dirt, etc.

 

 

 

 

10ºC to +40ºC

recorder

 

 

 

 

 

 

 

(14ºF to 104ºF),

 

General

 

 

 

 

 

 

non-freezing

 

 

 

 

 

 

 

Ambient humidity:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90% or less,

 

 

 

 

 

 

 

 

non-condensing.

 

 

Overall unit

Check for unusual

$

 

 

Visual and auditory

No fault.

 

 

vibration and noise.

 

 

checks.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Measure voltage

Within permissible

 

 

Power

 

 

 

 

AC voltage

 

 

Check that main circuit

 

 

 

across inverter

Meter, digital

 

supply

$

 

 

fluctuation

 

voltage is normal.

 

 

terminals R-S-T

multimeter

 

voltage

 

 

 

(Refer to page

 

 

 

 

 

L1-L2-L3.

 

 

 

 

 

 

 

184)

 

 

 

 

 

 

 

 

 

 

 

(1) Check with megger

 

 

$

(1) Disconnect all

 

 

 

 

(across main circuit

 

 

 

cables from

 

 

 

 

terminals and

 

 

 

inverter and

 

 

 

 

ground terminal).

 

 

 

measure across

 

 

 

 

(2) Check for loose

 

$

 

terminals R, S, T,

(1) 5M or more.

500VDC class

 

General

screws and bolts.

 

 

 

U, V, W L1, L2, L3,

 

 

(3) Check for overheat-

 

$

 

U, V, Wand

(2), (3) No fault.

megger

 

 

 

 

 

 

Main

 

ing of each part.

 

 

 

ground terminal

 

 

 

(4) Clean.

 

$

 

with megger.

 

 

circuit

 

 

 

 

 

 

 

 

 

 

(2) Re-tighten.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3) Visual check.

 

 

 

 

(1) Check conductors

 

$

 

 

 

 

 

Conductors,

for distortion.

 

 

 

(1), (2) Visual check.

(1), (2) No fault.

 

 

cables

(2) Check cable sheaths

 

$

 

 

 

 

 

 

 

 

 

 

for breakage.

 

 

 

 

 

 

 

Terminal

Check for damage.

 

$

 

Visual check.

No fault

 

 

block

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* For periodic inspection, consult Mitsubishi.

177

Page 191
Image 191
Mitsumi electronic FR-F520-0.75K Insulation resistance test using megger, Pressure test, Daily and Periodic Inspection