4.2.50 User initial value setting (Pr. 199)

Pr. 199 "user's initial value setting"

Related parameter

Pr. 77 "parameter write disable selection"

Among the parameters, you can set user-only parameter initial values. These values may be set to 16 parameters.

By performing user clear operation from the operation panel or parameter unit, you can initialize the parameters to the user-set initial values. Note that the parameters of which initial values have not been set are initialized to the factory settings by user clear operation.

#You can read the user's initial value list in the help mode of the parameter unit (FR-PU04).

Parameter

Factory

Setting Range

Number

Setting

 

199

0

0 to 999, 9999

The read Pr. 199 value is displayed as the number of parameters registered.

<Setting example>

(1)To set "1" in Pr. 7 and "2" in Pr. 8 as user's initial values. (Operation from the FR-DU04)

1)Set "1" (target initial value) in Pr. 7.

2)Set "2" (target initial value) in Pr. 8.

3)Press the SET key to read Pr. 199.

The number of parameters having user's initial values are then displayed.

4)Further press the SET key for 1.5 seconds. The parameter setting screen is then displayed.

5)Select Pr. 7 and Pr. 8 with the key and

press the SET key for 1.5 seconds to enter.

6)Through the above steps, the initial values of Pr. 7 and Pr. 8 are registered.

The settings of the parameters whose numbers are set in Pr. 199 (i.e. Pr. 7 = 1, Pr. 8 = 2 in the above example) are user's initial values.

(2) Deletion of user's initial values

By writing "9999" to Pr. 199 (and pressing the SET key for 1.5 seconds), the user's initial values registered are batch-deleted.

Note: 1. When user's initial values for Pr. 902 to Pr. 905 are set, one parameter uses the area of two parameters for registration.

2.As this setting is concerned with user-cleared initial values, the parameter numbers which cannot be cleared cannot be set.

3.The operation panel (FR-DU04) cannot be used to refer to user's initial values.

Pr. 240 % Refer to Pr. 72.