Mitsumi electronic FR-F520-0.75K, 55K instruction manual Switch-over mode, PU operation interlock

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 119
Image 119

PARAMETERS

(1) Switch-over mode

You can select between PU operation, external operation and computer link operation (when FR-A5NR option is used).

Operation Mode Switching

 

 

Switching Operation/Operating Status

 

1)

Select the PU operation mode.

External operation to PU

 

Rotation direction is the same as that of external operation.

operation

 

Set frequency is as set by the potentiometer (frequency setting potentiometer). (Note that

 

 

 

the setting will disappear when power is switched off or the inverter is reset.)

 

1)

Mode change command to computer link mode is transmitted from the computer.

External operation to computer

 

Rotation direction is the same as that of external operation.

link operation

 

Set frequency is as set by the potentiometer (frequency setting potentiometer). (Note that

 

 

 

the setting will disappear when power is switched off or the inverter is reset.)

PU operation to external

1)

Press the external operation key of the parameter unit.

 

Rotation direction is determined by the external operation input signal.

operation

 

 

Set frequency is determined by the external frequency setting signal.

 

 

PU operation to computer link

1)

Mode change command to computer link mode is transmitted from the computer.

operation

 

Rotation direction and set frequency are the same as those of PU operation.

Computer link operation to

1)

The switch-over command to the external mode is sent from the computer.

 

Rotation direction is determined by the external operation input signal.

external operation

 

 

Set frequency is determined by the external frequency setting signal.

 

 

Computer link operation to PU

1)

Select the PU operation mode with the operation panel or parameter unit.

operation

 

Rotation direction and set frequency are the same as those of computer link operation.

(2) PU operation interlock

When the PU operation interlock signal is switched off, the operation mode is forcibly changed to the external operation mode. This function prevents the inverter from being inoperative by the external command if the mode is accidentally left unswitched from the PU operation mode.

1)Preparation

Set "7" in Pr. 79 (PU operation interlock).

Using any of Pr. 180 to Pr. 186 (input terminal function selection), allocate the terminal used to input X12 (PU external interlock signal).

Refer to page 138 for Pr. 180 to Pr. 186 (input terminal function selection).

When the X12 signal is not assigned, the function of the MRS signal changes from MRS (output stop) to PU external interlock.

Note: When terminal assignment is changed using Pr. 180 to Pr. 186, the other functions may be affected. Check the functions of the corresponding terminals before making setting.

2) Function

X12 (MRS)

Function/Operation

Signal

 

 

Output stopped during external operation.

 

Operation mode can be switched to PU operation mode.

ON

Parameter values can be rewritten in PU operation

 

mode.

 

PU operation allowed.

 

Forcibly switched to external operation mode.

OFF

External operation allowed.

 

Switching to PU operation mode inhibited.

106

Page 119
Image 119
Mitsumi electronic FR-F520-0.75K, 55K Switch-over mode, PU operation interlock, X12 MRS Function/Operation