Roles of the magnetic contactors (MC1, MC2, MC3)

Magnetic

Place of Installation

Role

Contactor

 

 

MC1

Between power supply and

Normally shorted with the following exception:

inverter

Opened only when an inverter fault occurs (shorted again by resetting)

 

 

 

Shorted for commercial power supply operation, opened for inverter

MC2

Between power supply and motor

operation

Shorted when an inverter fault occurs (selected with parameter, except

 

 

 

 

for external thermal relay operation)

 

 

Shorted for inverter operation, opened for commercial power supply

MC3

Between inverter output and motor

operation

 

 

Opened when an inverter fault occurs

<I/O signals>

1) When this function is used (Pr. 135 = "1"), the input signals are switched on-off as indicated below:

 

Signal

Terminal Used

Function

On-Off

MC Operation ($: ON, : OFF)

 

 

 

MC1

MC2

MC3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Commercial power supply-

$

 

 

 

 

 

 

inverter operation enable

 

 

 

 

 

 

MRS

MRS

Operation

........................

ON

 

 

 

 

 

 

enable/disable selection

Commercial power supply-

$

Unchanged

 

 

 

 

 

 

 

 

 

 

 

inverter operation disable

 

 

 

 

 

 

 

 

 

........................

OFF

 

 

 

 

 

 

 

 

Inverter-commercial

Inverter operation

$

$

 

 

 

 

Depending on

 

ON

 

 

 

 

 

 

CS

power supply switch-

........................

 

 

 

 

 

 

Pr. 180 to Pr.186

Commercial power supply

$

$

 

 

 

 

over

 

 

 

 

 

operation

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter operation

Forward (reverse) rotation

$

$

 

 

 

STF

STF

command (invalid for

........................

ON

 

 

 

 

 

 

(STR)

(STR)

commercial power

Stop

OFF

$

$

 

 

 

 

 

supply) (Note)

 

 

 

 

 

 

 

 

OH

Depending on

External thermal relay

Motor normal ...

ON

$

 

 

 

Pr. 180 to Pr.186

input

Motor fault

OFF

 

 

 

 

 

 

 

 

 

Operating condition

Initialization

ON

Unchanged

Unchanged

 

 

 

RES

RES

Normal operation

$

 

 

 

initialization

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

........................

 

 

 

 

 

Note: In the above MC Operation field, [-] indicates that MC1 is on, MC2 is off and MC3 is on in inverter

 

 

 

operation and MC1 is on, MC2 is on and MC3 is off in commercial power supply operation.

 

 

 

[Unchanged] indicates that the status before signal-on or -off is held.

 

 

 

 

 

The CS signal only functions when the MRS signal is on. STF (STR) only functions when MRS and

4

 

 

CS are on.

 

 

 

 

 

 

 

MC1 switches off when an inverter fault occurs.

If the MRS signal is not switched on, neither commercial power supply nor inverter operation can be performed.

For the RES signal, reset input acceptance selection can be made using reset selection (Pr. 75).

2)The output signals are output as follows:

Signal

Terminal Used

Description

MC1

Depending on Pr. 190

MC1's operation signal is output

MC2

MC2's operation signal is output

to Pr. 195

MC3

MC3's operation signal is output

 

129