4.2.20 Output frequency detection (Pr. 42, Pr. 43, Pr. 50)

Pr. 42 "output frequency detection"

Pr. 43 "output frequency detection for reverse rotation"

Pr. 50 "second output frequency detection"

The output frequency signal (FU, FU2) is output when the output frequency reaches or exceeds the setting. This function can be used for electromagnetic brake operation, open signal, etc.

#You can also set the detection of the frequency used exclusively for reverse rotation. This function is effective for switching the timing of electromagnetic brake operation between forward rotation (rise) and reverse rotation (fall) during vertical lift operation, etc.

Parameter

Factory

Setting Range

Remarks

Number

Setting

 

 

42

6Hz

0 to 120Hz

 

43

9999

0 to 120Hz, 9999

9999: Same as Pr. 42

setting

 

 

 

50

30Hz

0 to 120Hz

 

<Setting>

Refer to the figure below and set the corresponding parameters:

When Pr. 43 9999, the Pr. 42 setting applies to forward rotation and the Pr. 43 setting applies to reverse rotation.

(Hz)

 

Forward

 

Pr.42

 

frequency

 

 

 

 

 

 

 

 

rotation

 

Pr.50

 

 

 

 

 

Time

Output

 

 

 

Reverse

Pr.43

 

 

 

rotation

Pr.50

 

 

 

 

 

 

 

 

 

Output signal

 

 

 

 

 

FU,FU2

OFF

ON

OFF

ON

OFF

Output Signal

Parameter Number

Output Signal

42

FU

43

 

50

FU2

Use Pr. 190 to Pr. 195 to assign the terminals used to output the FU2 signals.

Note: 1. When terminal assignment is changed using Pr. 190 to Pr. 195, the other functions may be affected. Check the functions of the corresponding terminals before making setting.

Pr. 44, Pr. 45 % Refer to Pr. 7.

Pr. 46 % Refer to Pr. 0.

Pr. 47 % Refer to Pr. 3.