PARAMETERS

(1) Wiring example

Sink logic, Pr. 185 = 7, Pr. 186 = 6, Pr. 192 = 17, Pr. 193 = 18, Pr. 194 = 19

 

 

 

 

MC2

 

 

 

 

Inverter

 

External

NFB

MC1

MC3

thermal relay

 

 

R L1

U

 

 

 

 

 

 

S L2

V

 

 

 

IM

 

 

T L3

W

 

 

 

 

 

 

R1 L11

 

 

 

 

Inverter start

 

S1 L21SU

 

Signal set in Pr. 190 to Pr. 195

(forward rotation)

 

STF

IPF

*1

 

MC

 

Inverter-commercial

 

 

 

 

 

MC3

1

*2

power supply switch-over

 

CS

OL

*1

MC

 

DC24V

Operation interlock

 

MRS

*1

MC2

2

 

 

FU

MC

 

 

 

OH *3

 

External thermal relay

 

 

 

3

 

Reset

 

RES

SE

 

 

 

 

 

 

SD

 

 

 

 

 

Frequency setting signal

 

10

 

 

 

 

 

 

2

 

IPF

 

 

 

 

 

5

 

 

 

 

 

 

 

OL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FU

 

 

DC

 

 

 

 

 

 

 

 

 

 

 

SE

 

24V

Note: !This switch-over function is used in the external operation mode. Always connect terminals R1, S1 (L11, L21) to a different power supply (power supply different from the one for MC1) to ensure proper operation.

!MC2 and MC3 must be mechanically interlocked.

*1. Note the sequence output terminal capacities. The terminals used depend on the Pr. 190 to Pr. 194 settings.

Output Terminal Capacity

Permissible Output Terminal Load

Inverter's open collector outputs

24VDC 0.1A

(IPF, OL, FU)

 

 

 

FR-A5AR (option output)

230VAC 0.3A

30VDC 0.3A

 

 

 

*2. When connecting an AC power supply, connect the FR-A5AR option and use the contact output.

When connecting a DC power supply, install the following protective diode.

*3. The terminals used depend on the Pr. 180 to Pr. 186 settings.

128

Page 141
Image 141
Mitsumi electronic FR-F520-0.75K, 55K instruction manual Sink logic, Pr = 7, Pr = 6, Pr = 17, Pr = 18, Pr =, NFB MC1