Mitsumi electronic FR-F520-0.75K, 55K Pr to Pr % Refer to Pr Pr , Pr % Refer to Pr

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 145
Image 145

PARAMETERS

Note: 1. This function is only activated when R1 and S1 are connected to a different power supply (power supply which is not connected to MC1).

2.This function is only valid in the external operation or PU (speed command) and external (run command) operation mode when the Pr. 135 value is other than "0". When the Pr. 135 value is other than "0" in the operation mode other than the above, MC1 and MC3 switch on.

3.MC3 is on when the MRS and CS signals are on and STR is off, but when the motor run by the commercial power supply was coasted to a stop at the last time, it restarts after the time set in Pr. 137 has elapsed.

4.Inverter operation is enabled when the MRS, STF and CS signals switch on. In other cases (MRS is on), commercial power supply operation is performed.

5.When the CS signal is switched off, the motor is switched over to commercial power supply operation. Note that when the STF (STR) signal is switched off, the motor is decelerated to a stop by the inverter.

6.When both MC2 and MC3 are off and MC2 or MC3 is then switched on, the motor restarts after the waiting time set in Pr. 136 has elapsed.

7.If the Pr. 135 setting is other than 0, the Pr. 136 and Pr. 137 settings are ignored in the PU operation mode.

Also, the inverter's input terminals (STF, CS, MRS, OH) return to their ordinary functions.

8.When the commercial power supply-inverter switch-over sequence is selected, the PU operation interlock function (Pr. 79 = 7) is not activated if it has been set.

9.When the terminal functions are changed using Pr. 180 to Pr. 186 and/or Pr. 190 to Pr. 195, the other functions may be affected. Confirm the functions of the corresponding terminals before making settings.

Pr. 140 to Pr. 143 % Refer to Pr. 29.

Pr. 144 % Refer to Pr. 37.

Pr. 148, Pr. 149 % Refer to Pr. 22.

132

Page 145
Image 145
Mitsumi electronic FR-F520-0.75K, 55K instruction manual Pr to Pr % Refer to Pr Pr , Pr % Refer to Pr