PARAMETERS

#You can set the output frequency of the inverter-operated motor at which the commercial power supply operation motors start. When the output frequency higher than the preset value continues for longer than the time set in Pr. 515, the commercial power supply motors start. In this case, the starting sequence depends on the pattern in Pr. 501. Here, the Pr. 509 value means the set value at which the commercial power supply motors start when the number of commercial power supply motors running is 0.

Parameter Number

Name

Setting Range

Setting Increments

 

Factory Setting

 

 

 

<EC version>

 

 

 

 

 

 

 

 

 

509

Auxiliary motor 1 starting frequency

0 to 120Hz

0.01Hz

 

60Hz

 

 

 

 

<50Hz>

 

 

 

 

 

 

 

 

 

510

Auxiliary motor 2 starting frequency

0 to 120Hz

0.01Hz

 

60Hz

 

 

 

 

<50Hz>

 

 

 

 

 

 

 

 

 

511

Auxiliary motor 3 starting frequency

0 to 120Hz

0.01Hz

 

60Hz

 

 

 

 

<50Hz>

 

 

 

 

 

 

 

 

 

#You can set the output frequency of the inverter-operated motor at which the commercial power supply

 

operation motors stop. When the output frequency lower than the preset value continues for longer than the

 

time set in Pr. 516, the commercial power supply motors stop. In this case, the stopping sequence depends

 

on the pattern in Pr. 501. Here, the Pr. 512 value means the set value at which the commercial power

 

supply motors stop when the number of commercial power supply motors running is 1.

 

 

 

 

 

 

 

 

 

Parameter Number

Name

Setting Range

Setting Increments

 

Factory Setting

 

 

512

Auxiliary motor 1 stopping frequency

0 to 120Hz

0.01Hz

 

0Hz

 

 

513

Auxiliary motor 2 stopping frequency

0 to 120Hz

0.01Hz

 

0Hz

 

 

514

Auxiliary motor 3 stopping frequency

0 to 120Hz

0.01Hz

 

0Hz

 

 

#You can set the delay time until the auxiliary motor is started. The auxiliary motor starts actually when the

 

time set in Pr. 515 elapses after the output frequency of the inverter operation motor has risen to or above

 

the value set in any of Pr. 509 to Pr. 511.

 

 

 

 

 

 

 

 

 

 

 

 

Parameter Number

Name

Setting Range

Setting Increments

 

Factory Setting

 

 

515

Auxiliary motor start delay time

0 to 3600s

0.1s

 

5s

 

 

#You can set the delay time until the auxiliary motor is stopped. The auxiliary motor stops actually when the

 

time set in Pr. 516 elapses after the output frequency of the inverter operation motor has dropped to or

 

below the value set in any of Pr. 512 to Pr. 514.

 

 

 

 

 

 

 

 

 

 

 

 

Parameter Number

Name

Setting Range

Setting Increments

 

Factory Setting

 

 

516

Auxiliary motor stop delay time

0 to 3600s

0.1s

 

5s

 

 

#You can set the MC switching interlock time (e.g. time from when RI01 turns off until R01 turns on) when

 

Pr. 501 = 2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter Number

Name

Setting Range

Setting Increments

 

Factory Setting

 

4

502

MC switching interlock time

0 to 100s

0.1s

 

1s

 

 

 

 

#You can set the time from MC switch-over to a start (time from when RI01 turns off and RI02 turns on until

 

inverter output starts) when Pr. 501 = 2. Set this time a little longer than the MC switching time.

 

 

 

 

 

 

 

Parameter Number

Name

Setting Range

Setting Increments

 

Factory Setting

 

 

503

Start waiting time

0 to 100s

0.1s

 

1s

 

 

#You can set the deceleration time until the output frequency varies by the decrement = Pr. 509 to Pr. 512

 

(for M2) if a motor connection occurs under advanced PID control. When the setting is 9999, the output

 

frequency is not forcibly changed.

 

 

 

 

 

 

 

 

 

 

 

 

Parameter Number

Name

Setting Range

Setting Increments

 

Factory Setting

 

 

504

Auxiliary motor connection-time

0 to 3600s

0.1s/0.01s

 

1s

 

 

deceleration time

 

 

 

 

 

 

 

 

 

 

#You can set the acceleration time until the output frequency varies by the increment = Pr. 509 to Pr. 512 (for M2) if a motor disconnection occurs under advanced PID control. When the setting is 9999, the output frequency is not forcibly changed.

Parameter Number

Name

Setting Range

Setting Increments

Factory Setting

505

Auxiliary motor disconnection-time

0 to 3600s, 9999

0.1s/0.01s

1s

acceleration time

 

 

 

 

151

Page 164
Image 164
Mitsumi electronic 55K, FR-F520-0.75K instruction manual Name Setting Range