Mitsumi electronic 55K, FR-F520-0.75K instruction manual Type, Terminal Name Description, Run, Ipf

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 22
Image 22

 

 

 

 

 

 

 

 

INSTALLATION AND WIRING

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

Symbol

Terminal Name

 

 

 

 

Description

 

 

 

 

 

10E

 

10VDC, permissible load

 

When the frequency setting potentiometer is

 

 

 

 

current 10mA

 

 

connected in the factory-set state, connect it to

 

 

 

 

Frequency setting

 

 

 

 

 

 

 

 

 

 

terminal 10.

 

 

 

 

 

 

power supply

5VDC, permissible load current

 

 

 

 

 

 

10

 

When it is connected to terminal 10E, change the

 

 

 

 

 

10mA

 

 

input specifications of terminal 2.

 

 

setting

 

 

 

 

 

 

 

 

 

 

By entering 0 to 5VDC (0 to 10VDC), the maximum output frequency is reached at 5V

 

 

 

 

 

 

 

 

2

Frequency setting

(or 10V) and I/O are proportional. Switch between input 0 to 5VDC (factory setting)

 

 

Frequency

(voltage)

and 0 to 10VDC from the operation panel. Input resistance 10k

. Maximum

 

Analog

 

 

 

 

permissible voltage 20V.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency setting

By entering 4 to 20mADC, the maximum output frequency is reached at 20mA and

 

 

 

4

I/O is proportional. This input signal is valid only when the AU signal is on. Input

 

 

 

(current)

 

 

 

 

resistance approximately 250. Maximum permissible current 30mA.

 

 

 

 

 

 

 

 

 

 

By entering 0 to ± 5VDC or 0 to ± 10VDC, this signal is added to the frequency setting

 

 

 

1

Auxiliary frequency

signal of terminal 2 or 4. Switch between input 0 to ± 5VDC and 0 to ± 10VDC (factory

 

 

 

setting

setting) from the operation panel. Input resistance 10k. Maximum permissible

 

 

 

 

 

 

 

 

 

voltage ± 20V.

 

 

 

 

 

 

 

 

5

Frequency setting

Common to the frequency setting signal (terminal 2, 1 or 4) and analog output

 

 

 

input common

terminal AM. Do not earth.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact

 

 

1 contact output indicating that the output has been stopped by

 

 

 

 

 

the inverter protective function activated.

 

 

 

 

 

 

(continuity across A-C), normal: continuity across B-C

 

 

 

 

 

A, B, C

Alarm output

230VAC 0.3A, 30VDC 0.3A. Alarm: discontinuity across B-C

 

 

 

 

 

 

 

(discontinuity across A-C).

 

 

 

 

 

 

 

 

 

Switched low when the inverter output frequency is equal to or

 

 

 

 

RUN

Inverter running

higher than the starting frequency (factory set to 0.5Hz, variable).

 

 

 

 

Switched high during stop or DC injection brake operation (*1).

 

 

 

 

 

 

 

 

 

 

 

 

Permissible load 24VDC 0.1A.

 

 

 

Output terminal

 

 

 

 

 

Switched low when the output frequency has reached within

 

function selection

 

 

collectorOpen

SU

Up to frequency

± 10% of the set frequency (factory setting, variable). Switched

 

(Pr. 190 to

 

signalsOutput

high during acceleration, deceleration or stop (*1). Permissible

 

Pr. 195) change

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

load 24VDC 0.1A.

 

 

 

 

terminal

 

 

 

 

 

Switched low when the stall prevention function has caused stall

 

functions.

 

 

 

OL

Overload alarm

prevention to be activated. Switched high when stall prevention is

 

 

 

 

 

 

reset (*1). Permissible load 24VDC 0.1A.

 

 

 

 

 

IPF

Instantaneous power

Switched low when instantaneous power failure or undervoltage

 

 

 

 

 

failure

protection is activated (*1). Permissible load 24VDC 0.1A.

 

 

 

 

 

 

 

 

 

 

 

 

 

Switched low when the output frequency has reached or

 

 

 

 

 

FU

Frequency detection

exceeded the detection frequency set as appropriate. Switched

 

 

 

 

 

high when below the detection frequency (*1). Permissible load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24VDC 0.1A

 

 

 

 

 

 

 

 

SE

Open collector output

Common to the RUN, SU, OL, IPF and FU terminals.

 

 

 

 

 

 

common

 

 

 

 

 

 

 

 

 

Pulse

 

 

One selected from 16

 

 

Factory setting of output item:

 

 

 

 

FM

For meter

monitoring items, such as

 

Frequency permissible load current 2mA

 

 

 

 

 

 

 

 

 

output frequency, is output. (*2)

 

1440 pulses/s at 60Hz

 

 

 

 

Analog

 

 

The output signal is

 

 

Factory setting of output item:

 

 

 

 

 

 

of each monitoring item.

 

 

Permissible load current 1mA

 

 

 

AM

Analog signal output

proportional to the magnitude

 

Frequency output signal 0 to 10VDC

 

Communication

485-RS

 

 

With the operation panel connector, communication can be made through RS-485.

 

 

 

 

 

 

 

 

 

 

Conforming Standard : EIA Standard RS-485

 

 

 

 

 



PU connector

Transmission format

: Multi-drop link

 

 

 

 

 

 

 

Communication speed: Maximum 19200bps

 

 

 

 

 

 

 

Overall length

: 500m (1640.40feet)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1: Low indicates that the open collector-outputting transistor is on (conducts). High indicates that the transistor is off (does not conduct).

*2: Not output while the inverter is reset.