PROTECTIVE FUNCTIONS

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.UVT

 

FR-PU04

 

Under Voltage

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

Name

Undervoltage protection

 

 

 

 

 

 

If the power supply voltage of the inverter reduces, the control circuit will not

 

 

 

operate properly and will result in decreased motor torque or increased heat

 

 

Description

generation. To prevent this, if the power supply voltage reduces below 150V

 

 

(approximately 300V for the 400V class), this function stops the inverter output.

 

 

 

 

 

 

When a jumper is not connected across P-P1 <+ - P1>, the undervoltage

 

 

 

protective function is activated.

 

 

 

Check point

Check for start of large-capacity motor.

 

 

 

Check that a jumper or DC reactor is connected across terminals P-P1 <+ - P1>.

 

 

 

 

 

Corrective action

Check the power supply system equipment such as power supply.

 

 

Connect a jumper or DC reactor across terminals P-P1 <+ - P1>.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

 

E.FIN

 

FR-PU04

 

H/Sink O/Temp

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

Fin overheat

 

 

 

 

 

Description

If the cooling fin overheats, the overheat sensor is actuated to stop the inverter

 

 

output.

 

 

 

 

 

 

 

 

 

 

 

Check point

Check for too high ambient temperature.

 

 

 

Check for cooling fin clogging.

 

 

 

 

 

 

 

Corrective action

Set the ambient temperature to within the specifications.

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

 

E.GF

 

FR-PU04

 

Ground Fault

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

Output side ground fault overcurrent protection

 

 

 

Description

This function stops the inverter output if a ground fault overcurrent flows due to

 

 

a ground fault which occurred in the inverter's output (load) side.

 

 

 

 

 

Check point

Check for a ground fault in the motor and connection cable.

 

 

Corrective action

Remedy the ground fault portion.

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.OHT

 

FR-PU04

 

OH Fault

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

Name

External thermal relay operation (Note 3)

 

 

 

 

If the external thermal relay designed for motor overheat protection or the

 

 

Description

internally mounted temperature relay in the motor switches on (contacts open),

 

 

the inverter output is stopped. If the relay contacts are reset automatically, the

 

 

 

 

 

 

inverter will not restart unless it is reset.

 

 

 

 

Check for motor overheating.

 

 

 

Check point

Check that the value of 7 (OH signal) is set correctly in any of Pr. 180 to

 

 

 

 

Pr. 186 (input terminal function selection).

 

 

 

Corrective action

Reduce the load and operating duty.

 

 

Note 3: This function is activated only when OH has been set to any of Pr. 180 to Pr. 186 (input terminal function selection).