2.3 Other wiring

INSTALLATION AND WIRING

2.3.1 Power harmonics

Power harmonics may be generated from the converter section of the inverter, affecting power supply equipment, power capacitors, etc. Power harmonics are different in generation source, frequency and transmission path from radio frequency (RF) noise and leakage currents. Take the following counter measures.

The differences between harmonics and RF noise are indicated below:

Item

Harmonics

RF Noise

Frequency

Normally 40th to 50th degrees or less, (up

High frequency (several 10kHz to MHz order)

 

to 3kHz or less)

 

Environment

To wire paths, power impedance

Across spaces, distance, laying paths

Quantitative understanding

Logical computation is possible

Occurs randomly, quantitative understanding is difficult.

Generated amount

Approximately proportional to load capacity

According to current fluctuation rate (larger with faster

switching)

 

 

Immunity of affected device

Specified in standards for each device.

Differs according to maker’s device specifications.

Example of safeguard

Install a reactor

Increase the distance.

 

 

 

Safeguard

The harmonic current generated from the inverter to the power supply differs according to various conditions such as the wiring impedance, whether a power factor improving reactor is used or not, and output frequency and output current on the load side.

For the output frequency and output current, the adequate method is to obtain them under rated load at the maximum operating frequency.

 

 

 

 

Power factor

 

 

 

 

improving DC

 

 

 

NFB

 

 

 

reactor

 

 

 

Motor

Inverter IM

2

Power factor

Do not insert power factor

improving AC

improving capacitor

reactor

 

Note: A power factor improving capacitor or surge suppressor on the inverter’s output may overheat or be damaged due to the harmonics of the inverter output. Also, since the overcurrent protection is activated by an overcurrent that flows in the inverter, do not insert a capacitor or surge suppressor on the inverter's output when the motor is inverter-driven. To improve the power factor, insert a power factor improving reactor in the inverter’s input or DC circuit. For details, refer to the technical information.