INSTALLATION AND WIRING

2.3.6 Peripheral devices

(1) Selection of peripheral devices

Check the capacity of the motor to be used with the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity.

Refer to the following list and prepare appropriate peripheral devices:

1) 200V class

 

Motor

Power

Rated current of Circuit Breaker (Note)

 

 

Supply

 

 

 

 

Magnetic

Inverter Type

Output

 

 

With power factor

Capacity

Standard

Contactor

 

(kW (HP))

improving reactor

 

(kVA)

 

 

 

 

 

 

 

 

 

 

 

FR-F520-0.75K

0.75 (1)

2.1

30AF

10A

30AF

10A

S-N10

FR-F520-1.5K

1.5 (2)

4.0

30AF

15A

30AF

15A

S-N10

FR-F520-2.2K

2.2 (3)

4.8

30AF

20A

30AF

15A

S-N11,S-N12

FR-F520-3.7K

3.7 (5)

8

30AF

30A

30AF

30A

S-N20

FR-F520-5.5K

5.5

(7.5)

11.5

50AF

50A

50AF

40A

S-N25

FR-F520-7.5K

7.5 (10)

16

100AF 60A

50AF

50A

S-N35

FR-F520-11K

11

(15)

20

100AF 75A

100AF 75A

S-N50

FR-F520-15K

15

(20)

27

225AF

125A

100AF

100A

S-N65

FR-F520-18.5K

18.5 (25)

32

225AF

150A

225AF

125A

S-N80

FR-F520-22K

22

(30)

41

225AF

175A

225AF

150A

S-N95

FR-F520-30K

30

(40)

52

225AF

225A

225AF

175A

S-N125

FR-F520-37K

37

(50)

65

400AF

250A

225AF

225A

S-N150

FR-F520-45K

45

(60)

79

400AF

300A

400AF

300A

S-N180

FR-F520-55K

55

(75)

99

400AF

400A

400AF

350A

S-N220

2) 400V class

 

Motor

Power

Rated current of Circuit Breaker (Note)

 

 

Supply

 

 

 

 

Magnetic

Inverter Type

Output

 

 

With power factor

Capacity

Standard

Contactor

 

(kW (HP))

improving reactor

 

(kVA)

 

 

 

 

 

 

 

 

 

 

 

FR-F540-0.75K

0.75 (1)

2.1

30AF 5A

30AF 5A

S-N10

FR-F540-1.5K

1.5 (2)

4.0

30AF

10A

30AF

10A

S-N10

FR-F540-2.2K

2.2 (3)

4.8

30AF

15A

30AF

10A

S-N11,S-N12

FR-F540-3.7K

3.7 (5)

8

30AF

20A

30AF

15A

S-N20

FR-F540-5.5K

5.5

(7.5)

11.5

30AF

30A

30AF

20A

S-N20

FR-F540-7.5K

7.5 (10)

16

30AF

30A

30AF

30A

S-N20

FR-F540-11K

11

(15)

20

50AF

50A

50AF

40A

S-N20

FR-F540-15K

15

(20)

27

100AF 60A

50AF

50A

S-N25

FR-F540-18.5K

18.5 (25)

32

100AF 75A

100AF 60A

S-N35

FR-F540-22K

22

(30)

41

100AF

100A

100AF 75A

S-N50

FR-F540-30K

30

(40)

52

225AF

125A

100AF

100A

S-N65

FR-F540-37K

37

(50)

65

225AF

150A

225AF

125A

S-N80

FR-F540-45K

45

(60)

79

225AF

175A

225AF

150A

S-N80

FR-F540-55K

55

(75)

99

225AF

200A

225AF

175A

S-N125