PARAMETERS

<Setting>

Refer to the figures in the previous page and following table, and set the parameters:

Parameter

 

Setting

 

Description

Number

 

 

 

 

 

 

 

 

 

0

Frequency search made

 

 

 

 

Frequency search is made after detection of an instantaneous power failure.

 

 

 

162

 

 

No frequency search

 

 

 

 

1

Independently of the motor coasting speed, the output voltage is gradually increased

 

 

 

with the frequency kept as preset.

 

 

 

 

0.75K to 1.5K

0.5 s coasting time

 

 

 

0

2.2K to 7.5K

1.0 s coasting time

 

Generally use this setting.

 

 

11K or more

3.0 s coasting time

 

 

57

 

 

Waiting time for inverter-triggered restart after power is restored from an instantaneous

 

 

0.1 to 5 s

power failure. (Set this time between 0.1 s and 5 s according to the inertia moment (J)

 

 

 

and torque of the load.)

 

 

 

 

9999

No restart

 

 

58

 

0 to 60 s

 

 

 

163

 

0 to 20 s

Normally the motor may be run with the factory settings. These values are adjustable

164

 

0 to 100%

to the load (inertia moment, torque).

 

 

165

 

0 to 150%

 

 

 

Note: 1. When restart operation is selected, UVT and IPF among the alarm output signals are not output at occurrence of an instantaneous power failure.

2.If the inverter capacity is more than one rank higher than the motor capacity, an overcurrent (OCT) alarm may take place, disabling the motor from starting.

3.When Pr. 57 9999, the inverter will not run if the CS signal remain off.

4.When Pr. 162 = "0", connection of two or more motors to one inverter will make the inverter function improperly. (The inverter will not start properly.)

5.When Pr. 162 = "0", the DC dynamic brake is operated instantly on detection of restarting speed. Therefore, if the inertia moment (J) of the load is small, the speed may reduce.

6.When Pr. 162 = "1", the output frequency before an instantaneous power failure is stored and output at the time of restart. If the power of the inverter control circuit is lost, the frequency before an instantaneous power failure cannot be stored and the inverter will start at 0Hz.

7.The SU and FU signals are not output during restart but are output after the restart cushion time has elapsed.

CAUTION

Provide mechanical interlocks for MC1 and MC2.

The inverter will be damaged if power is entered into the inverter output section.

When automatic restart after instantaneous power failure has been selected, the motor and machine will start suddenly (after the reset time has elapsed) after occurrence of an instantaneous power failure. Stay away from the motor and machine.

When you have selected automatic restart after instantaneous power failure, apply the supplied CAUTION seals in easily visible places.

90

Page 103
Image 103
Mitsumi electronic FR-F520-0.75K, 55K Parameter Setting Description, To the load inertia moment, torque 165