SPECIFICATIONS

 

 

 

 

 

 

 

 

 

Selection can be made from output frequency, motor current (steady or peak value), output

 

 

 

Operating

voltage, frequency setting, running speed, overload, converter output voltage (steady or peak

 

PU (FR-DU04

 

status

value), electronic overcurrent protection load factor, input power, output power, load meter,

 

/FR-PU04)

 

 

total energization time, actual operation time, total power and motor load factor.

Display

 

 

Alarm

Alarm definition is displayed when protective function is activated. 8 alarm definitions are stored.

 

 

definition

(Four alarm definitions are only displayed on the operation panel.)

 

 

 

 

Additional

 

Operating

Input terminal signal states, output terminal signal states, option fitting status, terminal

 

 

status

assignment status

 

display on

 

 

 

Alarm

Output voltage/current/frequency/cumulative ON time immediately before activation of

 

parameter unit

 

 

 

definition

protective function

 

(FR-PU04)

 

 

 

Interactive

 

 

only

 

Operation guide and troubleshooting by help function

 

 

guidance

 

 

 

 

 

 

 

 

Overcurrent shut-off (during acceleration, deceleration, constant speed), regenerative

 

 

 

 

overvoltage shut-off, undervoltage, instantaneous power failure, overload shut-off (electronic

Protective/alarm functions

overcurrent protection), ground fault current, output short circuit, main circuit device overheat,

stall prevention, overload alarm, fin overheat, fan fault, option fault, parameter error, PU

 

 

 

 

 

 

 

 

disconnection, retry count exceeded, output phase failure, CPU error, 24VDC power output

 

 

 

 

short circuit, operation panel power supply short circuit

 

Ambient temperature

-10°C to +50° C (14° F to 122° F) (non-freezing)

 

(-10°C to +40° C (14° F to 104° F) with FR-A5CV""attachment)

 

 

 

 

Environment

Ambient humidity

 

90%RH or less (non-condensing)

Storage temperature

-20°C to +65° C (-4°F to +149° F)

 

 

(Note 2)

 

 

 

 

 

Ambience

 

Indoors. (No corrosive and flammable gases, oil mist, dust and dirt.)

 

 

 

 

Maximum 1000m (3280.80feet) above sea level for standard operation.

 

Altitude, vibration

 

After that derate by 3% for every extra 500m (1640.40feet) up to 2500m (8202.00feet) (91%).

 

 

 

 

5.9 m/s2 or less (conforming to JIS C 0040)

Note: 1. Jog operation may also be performed from the operation panel or parameter unit. 2. Temperature applicable for a short period in transit, etc.