4.2.23 Monitoring reference (Pr. 55, Pr. 56)

Pr. 55 "frequency monitoring reference"

Pr. 56 "current monitoring reference"

Related parameters

Pr. 37 "speed display"

Pr. 53 "PU level display data selection" Pr. 54 "FM terminal function selection" Pr. 158 "AM terminal function selection"

Pr. 900 "FM terminal calibration" Pr. 901 "AM terminal calibration"

Set the frequency or current which is referenced for display when the frequency or current is selected for the FM and AM terminals and PU level meter display.

Parameter

Factory

 

 

 

Setting Range

 

 

Number

Setting

 

 

 

 

 

 

 

 

 

 

 

55

60Hz 50Hz

 

 

 

0 to 120Hz

 

 

56

Rated output

 

 

 

0 to 500A

 

 

current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1440 pulses/s. (terminal FM)

 

 

 

 

10VDC (terminal AM)

 

 

 

 

Full scale (PU level monitor)

 

 

 

 

 

 

 

 

Output or display

 

 

 

 

 

 

 

 

Output frequency Pr.55

 

 

 

 

Frequency setting

 

 

 

 

Running speed

1440 pulses/s. (terminal FM) 10VDC (terminal AM)

Full scale (PU level monitor)

Output or display

Output current

Pr.56

Output current peak value Load meter

<Setting>

Referring to the above figures and following table, set Pr. 55 and Pr. 56:

Monitoring Reference

 

PU Level Display

FM Terminal

AM Terminal

Monitored Data Selection

Selection

Function Selection

Function Selection

Setting Parameter

 

Pr. 53 Setting

Pr. 54 Setting

Pr. 158 Setting

 

 

Frequency monitoring

Output frequency (Hz)

1

1

1

Frequency setting (Hz)

5

5

5

reference Pr. 55

Running speed (Pr. 37)

6

6

6

 

 

Output current (A)

2

2

2

Current monitoring

Output current peak value

11

11

11

reference Pr. 56

(A)

 

 

 

 

Load meter (A)

17

17

17

 

 

Set to make the PU

Set to make the

Set to make the

Setting using Pr. 55, Pr. 56

level meter indication

terminal FM pulse train

terminal AM output

to be in full-scale.

output to be 1440

voltage to be 10V.

 

 

 

 

 

pulses/s.

 

Note: 1. The maximum pulse train output of terminal FM is 2400 pulses/s. If Pr. 55 is not adjusted, the output of terminal FM will be filled to capacity. Therefore, adjust Pr. 55.

2. The maximum output voltage of terminal AM is 10VDC.