Mitsumi electronic 55K, FR-F520-0.75K Harmonic suppression techniques, Acl, Dcl, Fr-Hc

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 42
Image 42

 

 

INSTALLATION AND WIRING

4) Harmonic suppression techniques

 

 

 

 

 

No.

Item

Description

1

Reactor installation

Install a reactor (ACL) in the AC side of the inverter or a reactor (DCL) in its DC side or both to

(ACL, DCL)

suppress outgoing harmonic currents.

 

 

High power factor

The converter circuit is switched on-off to convert an input current waveform into a sine wave,

2

converter

suppressing harmonic currents substantially. The high power factor converter (FR-HC) is used

 

(FR-HC)

with the standard accessory.

 

Installation of power

When used with a series reactor, the power factor improving capacitor has an effect of absorbing

3

factor improving

harmonic currents.

 

capacitor

 

 

 

 

4

Transformer multi-

Use two transformers with a phase angle difference of 30° as in

 

-, -combination to

 

phase operation

provide an effect corresponding to 12 pulses, reducing low-degree harmonic currents.

 

5

AC filter

A capacitor and a reactor are used together to reduce impedance at specific frequencies,

producing a great effect of absorbing harmonic currents.

 

 

 

 

This filter detects the current of a circuit generating a harmonic current and generates a

6

Active filter

harmonic current equivalent to a difference between that current and a fundamental wave

current to suppress a harmonic current at a detection point, providing a great effect of absorbing

 

 

 

 

harmonic currents.

31