Mitsumi electronic 55K Pr motor switch-over selection = 2 Direct Method, System configuration

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 160
Image 160

PARAMETERS

(3) Pr. 501 "motor switch-over selection" = "2" (Direct Method)

When the start signal is entered, the motor is started by the inverter. When the conditions for starting the next motor are enabled, the MCs between inverter and motor and between power supply and motor are switched over to change the inverter-driven motor to commercial power supply operation, starting the next motor by the inverter. Reversely, when the conditions for stopping the motors are enabled during running of several motors, the motors are stopped, beginning with the one started first (run by the commercial power supply).

Note: When the inverter is reset, the sequence of starting the motors to be driven returns to the initial status. (Pr. 501 = 1 or 2)

You cannot write values to Pr. 500 and Pr. 501 during operation. Also when the Pr. 500 or Pr. 501 setting is changed in a stop state, the sequence of starting the motors to be driven returns to the initial status.

<System configuration>

(1) Pr. 501 "motor switch-over selection" = 0 (Basic Method)

 

 

 

 

 

MC

Example

Distributed water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R04

M4

 

 

 

 

 

 

 

 

 

PUMP4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R03

M3

 

 

 

 

 

 

 

 

 

PUMP3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R02

M2

 

 

 

 

 

Inverter

 

 

PUMP2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

RST

UVW

 

 

M1

 

 

 

supply

 

 

 

 

 

 

 

 

 

 

 

 

PUMP1

 

 

 

 

 

 

 

 

 

 

 

Forward rotation

 

STF

 

 

 

 

 

 

 

Reverse rotation

 

STR

 

 

 

Supplied water

 

 

Advanced PID

X14

RT

 

 

 

 

 

 

 

control selection

X24

 

 

R02

 

 

 

 

 

PID forward-reverse

JOG

FU

MC

 

 

 

 

 

 

R02

 

 

 

 

action switching

 

R03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SD

OL

MC

 

 

 

 

 

 

 

 

 

R03

 

 

 

 

 

 

10

IPF

R04

MC

DC24V

 

 

4

Setting potentiometer

 

 

 

 

R04

For 2-wire type

Detector

 

2

SE

 

 

 

 

 

 

 

 

 

 

 

(Set point setting)

 

 

 

 

 

 

 

 

 

 

 

 

 

-

+

 

 

 

5

 

Sink logic

 

 

 

 

 

 

 

 

 

Deviation signal

 

1

 

When Pr. 183=14, Pr. 185=24,

 

 

 

 

 

Pr. 194=42, Pr. 193=43, Pr. 192=44

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

(Process value) 4 to 20mA

0Power 24V supply

147

Page 160
Image 160
Mitsumi electronic 55K, FR-F520-0.75K Pr motor switch-over selection = 2 Direct Method, System configuration