Operation Panel
Indication
Name
Operation Panel
Indication
Name
Description
Check point
Corrective action
Operation Panel
Indication
Name
Description
Check point
Corrective action

PROTECTIVE FUNCTIONS

E.THM

FR-PU04

Motor Overload

Motor overload shut-off (electronic overcurrent protection) (Note 1)

The electronic overcurrent protection in the inverter detects motor overheat due to overload or reduced cooling capability during constant-speed operation. When 85% of the preset value is reached, pre-alarm (TH indication) occurs. When the specified value is reached, the protective circuit is activated to stop the inverter output. When a special motor such as a multi-pole motor or two or more motors are run, provide a thermal relay in the inverter output side since the motor(s) cannot be protected by the electronic overcurrent protection.

Check the motor for use under overload.

Reduce the load weight.

For a constant-torque motor, change the Pr. 71 setting to the constant-torque motor setting.

E.THT

FR-PU04

Inv. Overload

Inverter overload shut-off (electronic overcurrent protection) (Note 1)

If a current of more than 120% of the rated output current flows and overcurrent shut-off does not occur (150% or less), inverse-time characteristics cause the electronic overcurrent protection to be activated to stop the inverter output in order to protect the output transistors.

(Overload immunity 120%, 60s.)

Check the motor for use under overload.

Reduce the load weight.

Note 1: Resetting the inverter initializes the internal heat integrating data of the electronic overcurrent protection.

E.IPF

FR-PU04

Inst. Pwr. Loss

 

Instantaneous power failure protection

 

If a power failure occurs for longer than 15ms (this also applies to inverter input

 

shut-off), the instantaneous power failure protective function is activated to stop

 

the inverter output in order to prevent the control circuit from malfunctioning. At

Description

this time, the alarm warning output contacts open (across terminals B-C) and

close (across terminals A-C). (Note 2) If a power failure persists for longer than

 

 

100ms, the alarm warning output is not provided, and the inverter restarts if the

 

start signal is on upon power restoration. (The inverter continues operating if an

 

instantaneous power failure is within 15ms.)

Check point

Find the cause of instantaneous power failure occurrence.

 

Remedy the instantaneous power failure.

Corrective action

Prepare a backup power supply for instantaneous power failure.

Set the function of automatic restart after instantaneous power failure. (Refer

 

 

 

to page 89.)

Note 2: When an instantaneous power failure occurs, the alarm display and alarm output are not provided, but the inverter performs protective operation to prevent a fault from occurring in itself. In some operating status (load size, acceleration/deceleration time setting, etc.), overcurrent or other protection may be activated upon power restoration.

165

Page 179
Image 179
Mitsumi electronic FR-F520-0.75K, 55K Instantaneous power failure is within 15ms, Remedy the instantaneous power failure