Related parameters
Pr. 9 "electronic thermal O/L relay" Pr. 48 "second stall prevention
operation current"
Pr. 49 "second stall prevention operation frequency"
Pr. 73 "0-5V/0-10V selection"
Pr. 156 "stall prevention operation selection"

PARAMETERS

4.2.12 Stall prevention (Pr. 22, Pr. 23, Pr. 66, Pr. 148, Pr. 149, Pr. 154)

Pr. 22 "stall prevention operation level" Pr. 23 "stall prevention operation level

compensation factor at double speed" Pr. 66 "stall prevention operation level reduction

starting frequency"

Pr. 148 "stall prevention operation level at 0V input" Pr. 149 "stall prevention operation level at 10V input"

Pr. 154 "voltage reduction selection during stall prevention operation"

#Set the output current level at which the output frequency is adjusted so that the inverter will not come to an alarm stop due to overcurrent etc.

#For high-speed operation at or over the more base frequency, acceleration may not be made because the motor current does not increase. To improve the operation characteristics of the motor in such a case, the stall prevention level in the high-frequency range can be reduced. This is effective for operation of a centrifugal separator up to the high-speed range. Normally, set 60Hz 50Hzin Pr. 66 and 100% in Pr. 23.

#In order to provide torque during stall prevention, Pr. 154 is factory-set not to reduce the output voltage. The setting of reducing the output voltage further decreases the probability of overcurrent trip occurrence.

#The stall prevention operation level can be varied by entering the analog signal into terminal 1.

Parameter Number

Factory Setting

Setting Range

Remarks

22

120%

0 to 150%, 9999

9999: Analog variable

23

9999

0 to 200%, 9999

9999: Constant according to Pr. 22

66

60Hz 50Hz

0 to 120Hz

 

148

120%

0 to 150%

(Bias)

149

150%

0 to 150%

(Gain)

154

1

0, 1

0: Output voltage reduced

1: Output voltage not reduced

 

 

 

Pr.22

 

 

Pr.23 = 9999

preventionStall operationlevel (%)

 

 

 

 

 

 

 

 

 

 

 

compensation factor (%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.23

 

 

 

 

 

 

 

 

 

 

Reduction ratio

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.66

120Hz Output

 

 

 

frequency (Hz)

Stall prevention

operation level (%)

(150%)

 

(120%)

 

 

Pr.149

Pr.148

 

 

 

 

 

0%

10(5)V

 

 

0V

Input voltage (V)

(across frequency setting terminals 1-5)

Setting example

(Pr.22=120%, Pr.23=100%, Pr.66=60Hz)

 

 

120

 

 

 

4

preventionStall

leveloperation(%)

112.5

 

 

 

 

 

 

 

90

 

 

 

 

 

 

 

 

 

 

 

 

75

 

 

 

 

 

 

0

60

80

100

120

 

 

 

 

 

Output

 

 

 

 

 

frequency (Hz)

77

Page 90