(5) Selection of load pattern (Pr. 14 "load pattern selection")

Used to select the output characteristic (V/F characteristic) according to the application and load characteristics.

Application

Setting

For constant torque load

0

(e.g. conveyor, cart)

 

For variable torque load

1

(fan, pump)

(Factory setting)

Note: When the RT terminal is ON, the second control functions (second acceleration/deceleration, second torque boost, second base frequency) are selected.

(6)When using a voltage input signal to perform operation (Pr. 73 "0 to 5V, 0 to 10V selection")

When using a voltage-input signal to perform operation, set the specifications of the frequency setting voltage signal entered to across terminals 2-5.

1)For 0 to 5VDC

Set "1" (factory setting) in Pr. 73.

2)For 0 to 10VDC Set "0" in Pr. 73.

When using a current input signal to perform operation

When using a current input signal to perform operation, input the signal to across terminals 4-5 and short terminals AU-SD.

(7) Setting of frequency setting voltage (current) gain (highest output frequency) (Pr. 903 "frequency setting voltage gain", Pr. 905 "frequency setting current gain")

For voltage signal: Pr. 903 "frequency setting voltage gain"

For current signal: Pr. 905 "frequency setting current gain"

When performing operation at any frequency higher than the following factory setting, change the corresponding parameter setting:

Parameter

Factory Setting

Pr. 903 "frequency setting voltage

60Hz at 5V (or 10V) DC

gain"

 

Pr. 905 "frequency setting current

(0Hz at 4mADC), 60Hz at

gain"

20mADC

When using the parameter unit to perform operation, the highest output frequency is the maximum frequency (factory-set to 120Hz). (Refer to Pr. 1 "maximum frequency".)

Note: When connecting a frequency meter across terminals FM-SD to monitor the running frequency, you must change the factory setting of Pr. 55 "frequency monitoring reference" to the highest frequency since the output of the FM terminal will be saturated at an output frequency of 100Hz or higher.

55