PARAMETERS

CAUTION

Always perform test operation.

Stall prevention operation performed during acceleration may increase the acceleration time.

Stall prevention operation performed during constant speed may cause sudden speed changes.

Stall prevention operation performed during deceleration may increase the deceleration time, increasing the deceleration distance.

4.2.45 OL signal output timer (Pr. 157)

Pr. 157 "OL signal waiting time"

Related parameters

Pr. 190 "RUN terminal function selection"

Pr. 191 "SU terminal function selection" Pr. 192 "IPF terminal function selection" Pr. 193 "OL terminal function selection" Pr. 194 "FU terminal function selection" Pr. 195 "A, B, C terminal function selection"

Use this parameter to set whether the overload alarm signal (OL signal) is output immediately or a preset period of time after occurrence of an overload status.

Parameter

Factory

Setting Range

Remarks

Number

Setting

 

 

157

0

0 to 25 s, 9999

9999: No signal output

Overload status (OL output)

OL output signal

Set time (s)

<Setting>

Refer to the following table and set the parameter:

Pr. 157

Description

Setting

 

0Output immediately.

0.1to 25 Output after the set time (s) has elapsed.

9999 Overload alarm signal is not output.

Pr. 158 % Refer to Pr. 54.

136