Mitsumi electronic 55K Operation procedure for running Operation pattern, Off Off →

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 144
Image 144

PARAMETERS

(3) Operation procedure

1)Operation procedure for running Operation pattern

Switch power on.

Set parameters.

Start, inverter operation

Constant-speed operation, commercial power supply operation

Deceleration (stop), inverter operation

!Pr. 135 = "1" (inverter's open collector output terminals)

!Pr. 136 = "2.0 s"

!Pr. 137 = "1.0 s" (Set the value equal to or longer than the time from when MC3 switches on actually until the inverter and

motor are connected. If it is shorter, restart may not function properly.)

!Pr. 57 = "0.5 s"

!Pr. 58 = "0.5 s" (Always set this parameter when commercial power

supply operation is switched to inverter operation.)

2) Signal on-off after parameter setting

 

MRS

CS

STF

MC1

MC2

MC3

Remarks

Power on

OFF

OFF

OFF

OFF

ON

OFF

OFF

ON

External operation mode

(OFF)

(OFF)

(OFF)

(OFF

ON)

(OFF)

(OFF

ON)

(PU operation mode)

 

At start

OFFON

OFF

ON

OFFON

ON

 

OFF

ON

 

(Inverter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

After MC3 switches off,

Constant speed

 

 

 

 

 

 

 

 

 

 

MC2 switches on.

(Commercial

ON

ON

OFF

ON

ON

 

OFF

ON

ON

OFF

(Motor coasts during this

power supply)

 

 

 

 

 

 

 

 

 

 

period.)

 

 

 

 

 

 

 

 

 

 

 

Waiting time 2s.

Switched to

 

 

 

 

 

 

 

 

 

 

After MC2 switches off,

inverter

 

 

 

 

 

 

 

 

 

 

MC3 switches on.

operation for

ON

OFF

ON

ON

ON

 

ON

OFF

OFF

ON

(Motor coasts during this

deceleration

 

 

 

 

 

 

 

 

 

 

period.)

(Inverter)

 

 

 

 

 

 

 

 

 

 

Waiting time 4s.

Stop

ON

ON

ONOFF

ON

 

OFF

ON

 

4

131

Page 144
Image 144
Mitsumi electronic 55K Operation procedure for running Operation pattern, Signal on-off after parameter setting