Mitsumi electronic 55K, FR-F520-0.75K Frequency jump Pr to Pr, Pr.3335Hz Pr.3430Hz

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 94
Image 94

PARAMETERS

4.2.16 Frequency jump (Pr. 31 to Pr. 36)

Pr. 31 "frequency jump 1A"

Pr. 32 "frequency jump 1B"

Pr. 33 "frequency jump 2A"

Pr. 34 "frequency jump 2B"

Pr. 35 "frequency jump 3A"

Pr. 36 "frequency jump 3B"

#When it is desired to avoid resonance attributable to the natural frequency of a mechanical system, these parameters allow resonant frequencies to be jumped. Up to three areas may be set, with the jump frequencies set to either the top or bottom point of each area.

#The value set to 1A, 2A or 3A is a jump point and operation is performed at this frequency.

Parameter

Factory

Setting Range

Remarks

Number

Setting

 

 

31

9999

0 to 120Hz, 9999

9999: Function invalid

32

9999

0 to 120Hz, 9999

9999: Function invalid

33

9999

0 to 120Hz, 9999

9999: Function invalid

34

9999

0 to 120Hz, 9999

9999: Function invalid

35

9999

0 to 120Hz, 9999

9999: Function invalid

36

9999

0 to 120Hz, 9999

9999: Function invalid

(Hz)

Frequency jump

Pr.36

Pr.35

frequency

Pr.34

Pr.33

Running

Pr.32

Pr.31

 

<Setting>

To fix the frequency at 30Hz between Pr. 33 and Pr. 34 (30Hz and 35Hz), set 30Hz in Pr. 33 and 35Hz in Pr. 34.

To jump to 35Hz between 30 and 35Hz, set 35Hz in Pr. 33 and 30Hz in Pr. 34.

Pr.34:35Hz

Pr.33:30Hz

Pr.33:35Hz

 

 

4

 

 

Pr.34:30Hz

 

 

 

 

 

 

 

 

Note: 1. During acceleration/deceleration, the running frequency within the set area is valid.