PARAMETERS

#PID control

PID actions are performed as set in Pr. 128 to Pr. 134 (PID control). (Refer to page 120)

In this advanced PID control, a voltage input (0 to ± 5V or 0 to ± 10V) may also be used as a process value.

Parameter Number

Name

Additional Setting

Description

Range

 

 

 

128

PID action selection

30, 31

30: PID reverse action

31: PID forward action

 

 

 

#PID forward-reverse action switching function

Use the X24 signal to switch between the forward and reverse actions under the control of the external signal. Assign the signal X24 to any terminal using any of Pr. 180 to Pr. 186 (input terminal function selection). (Refer to page 138)

Parameter Number

Name

Additional Setting

Description

Range

 

 

 

180 to 186

Input terminal function

24

X24 signal

selection

 

 

 

At PID reverse action setting (Pr. 128 = 10, 20, 30): Turning on the X24 signal starts a forward action.

A reverse action is performed when the X24 signal is off.

At PID forward action setting (Pr. 128 = 11, 21, 31): Turning on the X24 signal starts a reverse action.

A forward action is performed when the X24 signal is off.

#Assign the motor control signals (SLEEP, R01 to R04, RI01 to RI04) to Pr. 190 to Pr. 195 (output terminal function selection) or assign them to Pr. 320 to Pr. 322 (RA1, RA21, RA3 output selection) using the inboard option (FR-A5AR). (The functions of the output terminals are positive logic only.) (Refer to page 140)

Parameter Number

 

Name

 

 

 

190

RUN terminal function selection

 

 

 

191

SU terminal function selection

 

 

 

 

192

IPF terminal function selection

 

 

 

 

193

OL terminal function selection

 

 

 

 

194

FU terminal function selection

 

 

 

 

320

RA1 output selection (valid only when the FR-A5AR is used)

 

 

 

321

RA2 output selection (valid only when the FR-A5AR is used)

 

 

 

322

RA3 output selection (valid only when the FR-A5AR is used)

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional Setting

 

 

 

Description

 

 

Range

 

 

 

 

 

 

 

 

 

 

 

 

 

Set value

Signal name

 

Function

 

 

 

40

SLEEP

 

Output at stop

 

 

 

41

R01

 

Commercial power supply side motor 1 connection R01

 

 

 

42

R02

 

Commercial power supply side motor 2 connection R02

 

 

40, 41, 42, 43, 44, 45,

43

R03

 

Commercial power supply side motor 3 connection R03

 

 

46, 47, 48

44

R04

 

Commercial power supply side motor 4 connection R04

 

 

 

45

RI01

 

Inverter side motor 1 connection RI01

 

 

 

46

RI02

 

Inverter side motor 2 connection RI02

 

 

 

47

RI03

 

Inverter side motor 3 connection RI03

 

 

 

48

RI04

 

Inverter side motor 4 connection RI04

 

 

149

Page 162
Image 162
Mitsumi electronic 55K, FR-F520-0.75K Parameter Number Name Additional Setting Description, Signal name Function