Mitsumi electronic FR-F520-0.75K Pr motor switch-over selection = 0 Basic Method, Pr =0, Pr =1

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 159
Image 159

PARAMETERS

Flow rate Q

Qmax

Q3

Q2

Q1

(1) Pr. 501=0

Time

Motor 1 (M1)

 

 

Motor 2 (M2)

 

 

Motor 3 (M3)

 

 

Motor 4 (M4)

 

 

(Note)

 

(Note)

(2) Pr. 501=1

 

 

 

Motor 1 (M1)

 

 

Motor 2 (M2)

 

 

Motor 3 (M3)

 

 

Motor 4 (M4)

 

 

(3) Pr. 501=2

 

 

Motor 1 (M1)

 

 

Motor 2 (M2)

 

 

Motor 3 (M3)

 

 

Motor 4 (M4)

 

 

Inverter operation drive

Commercial power supply operation drive

Stop

(1) Pr. 501 "motor switch-over selection" = "0" (Basic Method)

The inverter-driven motor is always fixed, and the MCs between power supply and motors are turned on/off by the output frequency to increase/decrease the number of motors run by commercial power supply.

(2) Pr. 501 "motor switch-over selection" = "1" (Alternative Method)

During operation, as in the basic method (Pr. 501 = 0), the inverter-driven motor is fixed, and the number of motors run by commercial power supply is controlled by the output frequency. When the output is stopped by the sleep function, the MC between inverter and motor is switched over to change the inverter-driven motor.

Note: At this time, if the sequence of starting the motors was from M1 to M2 to M3 last time, it will be from M2 to M3 to M1 this time.

146

Page 159
Image 159
Mitsumi electronic FR-F520-0.75K, 55K Pr motor switch-over selection = 0 Basic Method, Pr =0, Pr =1, Pr =2