INSTALLATION AND WIRING

(5) Connecting the control circuit to a power supply separately from the main circuit

If the magnetic contactor (MC) in the inverter power supply is opened when the protective circuit is operated, the inverter control circuit power is lost and the alarm output signal cannot be kept on. To keep the alarm signal on terminals R1 and S1 are available. In this case, connect the power supply terminals R1 and S1 L11 and L21of the control circuit to the primary side of the MC.

Model FR-F520-0.75K to 3.7K, FR-F540-0.75K to 3.7K

<Connection procedure>

R

L1S〈 〉 T

L2 L3

S1 L21

R1 L11

Terminal block for main circuit

1)Loosen the upper screws

2)Remove the lower screws.

3)Remove the jumpers.

4)Connect the separate power supply cables for control circuit to the

lower terminals (R1, S1 L11, L21).

Model FR-F520-5.5K to 55K, FR-F540-5.5K to 55K

<Connection procedure>

 

 

R1

S1

 

 

L11〉 〈L21

 

 

 

 

 

 

Power supply terminal

 

 

 

 

 

 

 

 

 

 

 

 

block for control circuit

 

 

 

 

 

 

 

R

S

T

 

 

 

 

L1

L2

L3

 

 

 

 

MC

Main power supply

Power supply terminal block for control circuit

1)Loosen the upper screws.

2)Remove the lower screws.

3)Pull out and remove the jumper.

4)Connect the separate power supply

cables for control circuit to the

upper terminals (R1, S1 L11, L21). (Note 4)

Note: 1. When the main circuit power (R, S, T) L1 L2, L3is on, do not switch off the control power (terminals R1, S1 L11, L21). Otherwise the inverter may be damaged.

2.When using a separate power supply, the jumpers across R-R1 and S-S1 L1-L11and L2-L21must be removed. Otherwise the inverter may be damaged.

3.For a different power supply system, which takes the power of the control circuit from other than the primary side of the MC, the voltage should be equal to the main circuit voltage.

4.For the FR-F520-5.5K to 55K, FR-F540-5.5K to 55K, the power supply cables must not be connected to the lower terminals. If connected, the inverter may be damaged.

5.Supplying power to only terminals R1 L11and S1 L21and entering the start signal will result in an error display (E.OC1).

17

Page 28
Image 28
Mitsumi electronic Model FR-F520-0.75K to 3.7K, FR-F540-0.75K to 3.7K, Model FR-F520-5.5K to 55K, FR-F540-5.5K to 55K